conduit Phil and Ampacity
100


Where internal bonding means are provided between all entries, nonmetallic boxes shall be permitted to be used with metal raceways or metal-armored cables.




True 


Nonmetallic boxes can be used with metal raceways or metal-armored cables if internal bonding means are provided between all entries, ensuring proper grounding and safety.

100

What is the maximum allowable length for screws to extend when attaching a cover to a box?

3/8 inch 



100

Adjustment factors shall not apply to conductors in raceways having a length not exceeding _____.

24 inches

100

This article covers general requirements for conductors rated up to and including 2000V and their type designations, insulations, markings, mechanical strengths, ampacity ratings, and uses.

What is Article 310


Article 310 covers the general requirements for conductors rated up to and including 2000V, including their type designations, insulations, markings, mechanical strengths, ampacity ratings, and uses.

100

What is the ampacity of a #3/0 THWN conductor installed in an ambient temperature of 104 degrees Fahrenheit?

176 amps 


#3/0 THWN = 200a x .88 (104 degrees Fahrenheit) T.310.15(B)(2)(A) = 176a

200

Grounded conductors shall be permitted to be sized _____ than the ungrounded conductors.

Smaller 


Grounded conductors are permitted to be sized smaller than ungrounded conductors if they meet the requirements outlined in NEC sections 220.61 and 230.42 for service conductors or 215.2 and 220.61 for feeder conductors.

200

Boxes, conduit bodies, outlet box hoods, and fittings installed in wet locations shall be _____ for use in wet locations.


Listed 


Boxes, conduit bodies, outlet box hoods, and fittings installed in wet locations must be listed for use in wet locations to ensure compliance with safety standards.

200

Insulated conductors or cables used where exposed to direct rays of the sun shall be _____ as being sunlight resistant.

Listed 


Conductors or cables exposed to direct sunlight must be listed as being sunlight resistant to ensure they can withstand environmental conditions without degradation.

200

When using cable assemblies of Type NM or UF, it is essential that the sheath extends at least _____ inside the box and beyond the end of any cable clamp.

1/4 inch

200

How many #4 XHHW conductors can you install in a 2" flexible metal conduit?

16


Table 4 - 1.307 sq in.

Table 5 - .0814 sq in.

1.307/.0814 = 16 conductors

300

A _____ is an enclosure designed for surface mounting that has swinging doors or covers secured directly to and telescoping with the walls of the enclosure.

Cutout Box

300

For installations within walls or ceilings finished with noncombustible materials, ensure that the front edge of the box, plaster ring, extension ring, or listed extender is set back no more than _____ from the finished surface.

1/4 inch

300

Insulated conductors or cables used where exposed to direct rays of the sun shall be _____ as being sunlight resistant.

Listed

300

When splicing conductors, the distance from the entry of the raceway into the box to the opposite wall must be a minimum of _____ times the size of the largest raceway.


6

The National Electrical Code specifies that the minimum distance for splicing conductors is six times the size of the largest raceway to ensure proper spacing and avoid damage to conductor insulation.

 

300

The ampacity of a copper #10 THWN-2 is ____ when there are three conductors in the conduit and the ambient temperature is 70 degrees Fahrenheit

41.6 amps


 T.310.15(B)(16) = 40 amps X 1.04 correction factor = 41.6a.

400

Wiring methods that feature removable covers, such as wireways, multioutlet assemblies, and surface raceways, do not require the use of a(n) _____.

Box

400

 

Power monitoring or energy management equipment shall either be identified as a field installable accessory as part of the _____ equipment or be a _____ kit evaluated for field installation in switch or overcurrent device enclosures.


A) approved


listed 



400

In the designation 'THWN' for conductor insulation, what does the 'W' indicate it is permitted for?

Wet or damp locations 


The 'W' in 'THWN' indicates that the conductor is suitable for use in wet or damp locations, as specified in the National Electric Code.

400

This article covers general requirements for conductors rated up to and including 2000V and their type designations, insulations, markings, mechanical strengths, ampacity ratings, and uses.

Article 310

400

3" Intermediate Metal Conduit has a total square inch area of _______ square inches.

7.922 

Table 4 Total Area 100% = 7.922 sq in.

500

This article covers the installation and use of all boxes and conduit bodies used as outlet, device, junction, or pull boxes, depending on their use, and handhole enclosures.

This article covers the installation and use of all boxes and conduit bodies used as outlet, device, junction, or pull boxes, depending on their use, and handhole enclosures.

500

Boxes used at luminaire or lampholder outlets in or on a vertical surface shall be _____ on the interior of the box to indicate the maximum weight of the luminaire that is permitted to be supported by the box if other than 50 lb.

Identified and Marked

500

The cross-sectional area of a #1 Type A Rigid PVC conduit is _______ sq in.


1.084 


Table 4 @ 100% = 1.084

500

What is the ampacity of four #4/0 THWN copper current carrying conductors in a raceway installed through an ambient temperature of 45 degrees Celsius?

150.9 amps 


#4/0 THWN = 230a X 80% (T.310.15(B)(3)(a) = 184a X .82 (45 degrees Celsius) = 150.88a

500

Determine the allowable ampacity of 13 - #12 THHN conductors in a raceway, when passing through an area where the ambient temperature is 40 degrees Celsius.

13.65 amps 


#12 THHN = 30a x 50% (T.310.15(B)(3)(a) = 15a x .91 (40 degrees Celsius) = 13.65a