DCS
INSTRUMENTATION
SIS
WORK PROCESSES
FUN FACTS
100

What does 'DCS' stand for?

Distributed Control System

100

What does 'DVC' stand for?

Digital Valve Controller

100

What does 'SIS' stand for?

Safety Instrumented System

100

What does 'MOC' stand for?

Management of Change

100

What are the four pillars of Motiva culture?

We do the Right Thing

We are One Motiva

We are Empowered

We Deliver Excellence

200
What are the typically viewable parameters of a PID controller from an Operator graphic?

Tagname

Current mode, not in Normal mode

SP, PV, OP, VP

200

At Motiva, do flowmeters read standard or actual flow?

Standard

1.5X BONUS:

What is needed to calculate actual flow?

200

How are SIS instruments most easily identified in the field?

Transmitter caps painted red

Tagged as SIS tested

200

TRUE/FALSE?

Fuel Gas service control valves and orifice plates are only overhauled once failed

FALSE

1.5X BONUS:

On what frequency are they overhauled?

200

How many total fresh crude barrels per day does PAMC process?

660MBPD

300

A flow controller is measuring flow upstream of a control valve. 

What control action is necessary to control to setpoint correctly?

Reverse
300

If a flow transmitter is ranged 0-100"H2O, 0-50GPM, what will be the engineering unit range if re-ranged to 0-400"H2O?

0-100GPM

SQRT(100"/400") = 50GPM / X

Solve for X

300

What does 'M' stand for in Motiva's typical SIS nomenclature mean?

Median

1.5X BONUS:

Why do we use the median?

300

An old pneumatic positioner has failed. The team would like to install a DVC in its place.

How would this get accomplished?

Single Discipline MOC to upgrade

Business team approval for DVC, wiring and labor cost

Control valve bypassed

PSSR once installed and before returned to service

300

TRUE/FALSE

The first industrial DCS was built in 1959 at the Texaco Port Arthur refinery (now PAMC)

TRUE

This was an RW-300 Computer Console controller implemented by the Ramo-Wooldridge Company at FCCU3 and is in the Smithsonian Institute

400

What are at least two typical instrument/DCS communication protocols used at Motiva?

Profibus/Fieldbus (Serial), Modbus, 4-20 HART, Honeywell Digitally Enhanced (DE), Open Platform Communications (OPC)

400

A fail open valve using a 4-20mA signal and a 3-15psig air operating range is requested 25% valve position (output).

What current (mA) and air pressure (psig) is being used?

16mA, 12psig

400

How long can an SIS bypass be active?

72 Hours

400

Describe PID, APC, etc controller Uptime and Compliance

How does Motiva monitor PID, APC, etc controller Uptime and Compliance?

Uptime is a measure in percentage of time a controller is in its highest mode

Compliance is a measure in percentage of time that a controller's PV is within a programmed tolerance to SP

MDPro

400

What is the oldest running unit at PAMC?

VPS2

1.5X BONUS:

What year was VPS2 commissioned?

500

On the board, draw a typical Motiva fired heater control scheme.

Include instrumentation, control loops, overrides, etc.

Must Include:

Heater Outlet Thermocouple and Temperature Control

Fuel Gas Line, Orifice, Flow Control and Control Valve

Fuel Gas Pressure Tap, Transmitter and High/Low Overrides

O2 Analyzer and Low Override

500

Explain how a Guided Wave Radar works

Must Include:

Describe how instrument contacts process - guided probe, maybe non-contact radar

What type of signal - low energy microwave pulse down probe, or reflected radar signal

Measures time for signal to reflect from process surface - time domain reflectometry

Can perform interface because signal continues down probe or through space and second signal reflection will occur

500

What frequency does Motiva test SIS systems?

Is testing performed online or offline?

6 year frequency

Both

500

Provide three items to be entered in an 80/20 Turnaround scope prior to deadline

Provide three items to be entered in a Scope Input prior to deadline

80/20 - SIS valves via SLM, Fuel Gas service, GHG instruments, DVC Valve Scans, Control Valve Stroke test

Scope Input - CAREs, MOCs, MTAs, APC Needs, SIS Needs, Bad Actors

500

In 1903, what company was the original owner of what is now PAMC?

The Texas Company