100
What environmental condition affects the voltage of a PV module?

Ambient temperature, especially when cold

100

What formula can be used to find the maximum circuit current?

Isc x 1.25 = Max. Circuit Current

100

What is the main function of an inverter in a PV System?

Converts DC to AC electricity

100

What is bonding?

Connecting equipment to establish electrical conductivity / continuity

100

Calculate the maximum voltage of a REC 410W Alpha module installed in Seattle

52.79 V

(-7.2 - 25 = -32.2), then (-32.2 x -0.24% = 7.73%), then (1.0773 x 49.0 = 52.79)

200

According to NEC 690.7, what type of PV system is allowed the highest voltage?

Ground-mounts / carports (V limited only by equipment)

200

Why can we ignore the "125% factor" if a system uses an electrically-limited Electronic Power Converter?

The architecture of the equipment limits the amount of output current

200

How is the 120% rule used for interconnection?

When connecting via breaker, the allowable PV amperage is (Busbar Amps x 1.2) - Main Breaker Amps

200

What is the difference between Equipment Grounding Conductors (EGC) and Grounding Electrode Conductors (GEC)?

EGCs connect bonded metallic equipment together, and the GEC connects the system to the grounding electrode

200

Calculate the maximum voltage of a QCell Q.Peak Duo ML-G10+ 400W module installed in Spokane

50.46 V

300

When would professional engineering be necessary to calculate maximum voltage for a system?

When the system is ≥ 100 kW

300

Why might the current produced by a PV module be higher than its "nameplate rating"?

Nameplate current is based on STC irradiance of 1000 W/m2, so if irradiance is higher than that, the current will exceed the nameplate rating
300

Supply-side taps can occur anywhere between what two pieces of equipment?

Net meter and main service disconnect

300

Name one other type of grounding conductor, besides the standard rod

Ufer (concrete-encased), buried metal water pipes, ground rings, metal support structures

300

Calculate the maximum source current for a 420W REC Alpha Pure-R module

11.11 A

400

What is a temperature coefficient?

It measures how changes in temperature alter the voltage of a module or system

400

How is output current calculated for a microinverter system?

Microinverter output current x # of parallel microinverters in circuit

400

What rule must be followed to land a PV breaker anywhere in a service panel?

"Total Sources ≤ Busbar Rating"

400

What conductor conditions make faults more likely?

Nicked/chafed/pinched wires, thermal expansion, water exposure, improper installation

400

Calculate the output circuit current for a branch of (9) IQ8M Enphase microinverters

12.15 A

500

Why might it be difficult to identify the temperature coefficient on a cut sheet?

There is no standard label for the temperature coefficient (but TkVoc is common), other data points have their own temperature coefficients, TkVoc can be listed as a percentage or as "V per °C"

500

What type of module does not have a standard multiplying factor for calculating source circuit currents?

Bifacial modules

500

Compare/contrast string inverters and microinverters and give an example of when you would recommend one system over another.

Microinverters: 1 inverter per module, MPPT at module level, good for multiple roof faces or differential shading, can be expensive to replace

String Inverters: Single inverter for whole system, flexible location, "field-tested" for longer, usually easier to service... but inverter failure means whole system is down

500

What is the difference between ground and arc faults?

Ground = Exposed +/- conductor touches metallic equipment bonded to ground

Arc = Current "jumps" across a high-resistance failure point in the circuit

500

Calculate the output current for a branch of (12) IQ7X-96 Enphase microinverters

15.72 A

M