Article 517
Article 517
Article 517
Article 517
Article 517
100

Two ground-fault circuit-interrupter outlets ______ required in health care facility bathrooms or toilet rooms.

What is  c. shall not     517.21

100

Outside of patient care vicinities, the equipment grounding terminals of isolated ground receptacles installed in branch circuits for patient care _____ shall be connected to an insulated equipment grounding conductor in accordance with 250.146(D) installed in a wiring method described in 517.13(A).

a. vicinities

b. spaces

c. bathrooms

d. vicinities or spaces

What is b. spaces              517.16(B)(1)

100

Each patient bed location must be provided with how many receptacles? 

a. 3

b. 7

c. 14

d. 20

What is c. 14     517.19(B)(1) 

100

Essential electrical systems shall have _____ or more independent power sources. 

a. 1

b. 2

c. 3

d. 4

What is b. 2      517.30(A) 

100

The receptacles require in 517.19(B)(1) shall be permitted to be of the single, duplex, or quadruplex type or any combination of the _____. 

a. 1

b. 2

c. 3

d. 4

What is c. 3               517.19(B)(2)


200

Branch circuits serving fixed electrical equipment in patient care spaces shall be provided with a(an) _____ by installation in a metal raceway system or a cable having a metallic armor or sheath assembly.

What is effective ground-fault current path     517.13(A)


200

517 Part II, Health Care Facilities, applies to _____. 

What is d. none of the above        517.10

200

Type 1 and Type 2 essential electrical systems for health care facilities shall comprise separate branches capable of supplying a _____ amount of lighting and power service.

What is limited                    517.25

200

_____ requirements of 517.17 shall apply to buildings or portions of buildings containing health care facilities with Category 1 spaces. 

a. applicability

b. feeders

c. selectivity

d. testing

What is a. applicability        517.17(A)


200

Each patient bed location shall be supplied by at least _____ branch circuits. 

a. 1

b. 2

c. 3

d. 4

What is b. 2            517.18(A)

300

In patient care spaces, metal faceplates shall be connected to an effective ground-fault current path by means of _____ securing the faceplate to a metal yoke or strap of a receptacle or to a metal outlet box.

What is metal mounting screws      517.13(B)(1) Ex 2

300

Outside of patient care vicinities, care should be taken in specifying a system containing isolated ground receptacles in health care facilities because the _____ of the effective ground-fault current path is dependent upon the equipment grounding conductor(s) and does not benefit from any conduit or building structure in parallel with the equipment grounding conductor.

What is impedance             517.16(B)(2) Informational Note 2

300

517 Part II applies to _____ as determined by _____.

What is c. patient sleeping rooms, health care facility's governing body                                          517.10(A)

300

The receptacles required in 517.18(B)(1) shall be permitted to be the _____ type or any combination of the three.

a. single

b. duplex

c. quadruplex

d. all of the above

What is d. all of the above     517.18(B)(2) 


300

The busbar shall be securely fastened and installed in a _____ location.

What is accessible.       517.14


400

An isolated ground receptacle _____ installed in a patient care vicinity.

What is shall not be     517.16(A) 

400

In Category 2 spaces, each patient bed location of health care facilities shall be provided with a minimum of _____ receptacles. 

a. 2

b. 4

c. 6

d. 8

What is d. 8     517.18(B)(1)

400

Receptacles that are located within patient rooms, bathrooms, playrooms, and activity rooms of pediatric units or spaces similar shall be _____. 

a. listed and identified as TR

b. identified as tamper resistant

c. listed as tamper resistant

d. both B and C

What is d. both B and C     517.18(C)


400

What wire size must be used to bond normal and essential panels together that serve the same patient care facility?

What is c. 10 AWG     517.14

400

The reconditioning requirements of the code _____ apply to patient care-related electrical equipment. 

a. shall

b. shall not

c. may

d. may not

What is b. shall not.    517.6


500

In health care facilities, _____ ground receptacle(s) installed in patient care spaces outside of a patient care vicinity(s) shall comply with 517.16(B)(1) and (2).

What is isolated            517.16(B) 

500

When round-fault protection of equipment is first installed, each level shall be performance tested to ensure compliance with what Article?

What is 517.17(C)            517.17(D) 

500

The receptacles shall be permitted to be of the locking or nonlocking type and of the _____ in operating rooms. 

a. quadruplex type

b. single type

c. duplex type

d. any of the above


What is d. any of the above     517.19(C)(2)


500

The requirements of 517.29 through 517.35 shall apply to _____ essential electrical systems.

What is Type 1       517.29(A)

500

The insulated continuous conductor smaller than ____ shall be permitted on listed connections to an aluminum or copper 1/4", thick by 2" wide.

What is c. 10 AWG    517.14 Ex.