Ampacity
Definitions
Violation or Not
OCPD/ tap rules
Standard ratings
100

How many amps is #12 AWG CU THHN, good for ? 

20 amps 

100

single use devices that melt to interrupt excessive current

Fuses 

100

The grounded (neutral) conductor of a circuit is connected to a fuse.


Provide code reference 

❌ Violation

NEC Reference

240.22


The intentionally grounded conductor shall never be disconnected with an OCPD unless specified by Article 240.22(1) or (2).

100

A 3-phase feeder is protected by a 2-pole breaker opening only two ungrounded conductors.

Violation


 240.15(A) and (B)

100

85


Standard Rating or not 

NO


What size Breaker would you use ?

200

What size wire do you need for a 95 AMP circuit ?

#3

200

Resettable devices that trip when overcurrent is detected 

Circuit Breakers 

200

A subpanel is installed in a commercial locker room with showers. 


Violation or Not (provide NEC code reference)

violation

240.24(E)

200

according to article 240.4(B) What conditions must be met in order to use the next higher standard device rating 

240.4(B): Devices Rated 800A or Less 

The next higher standard overcurrent device rating above the ampacity of the conductors being protected shall be permitted when ALL of the following conditions are met: Branch Circuit Limitation ,Standard Rating Match ,800A Maximum 

(The next higher standard rating selected does not exceed 800 amperes)


200

175


Standard size or not 

yes standard 

What size wire would you feed this breaker with 

Aluminum ?  

300
What size wire would you run for a 40 amp circuit ? 

THHN CU

#8 

300

Define Available Fault Current 

the largest amount of current capable of being delivered at a specific point in an electrical system during a short-circuit condition

300

Available fault current is 28kA. A 10kA panelboard is installed downstream of a 65kA main breaker. No documentation or labeling is provided.

 Violation

 Series ratings must comply with 240.86(A) or (B).
Without proper documentation or tested combination marking, this is not permitted.

300

An outside feeder tap of 50 ft is installed by an electrician.

The disconnect is around the corner from the fuses protecting the tap conductors.

What specific part of the NEC code does this violate 

NEC Reference

240.21(B)(5)


The disconnect must be adjacent or integral to the OCPD when using the “outside taps of unlimited length” rule.

300

A conductor is calculated to an ampacity of 93 amps. Contractor puts them on a 100A breaker.

93A not a standard rating (see 240.6(A)).
240.4(B) permits next higher standard rating if conditions met and not exceeding 800A.

✅ Compliant (if conditions satisfied) 

NEC References

240.4(B)

240.6(A)

400

A contractor installs #12 copper THHN conductors supplying a 25A calculated load.

They protect the circuit with a 25-amp breaker.

NO  

Per 240.4(D)(6), #12 copper shall not be protected at more than 20A, unless specifically permitted elsewhere.

Load calculation does not override small conductor limits.

400

Define: Relays 

Electronic devices that monitor and control circuit protection

400

Available fault current is 22kA. Breaker interrupting rating is 14kA

❌ Violation 

NEC References

110.9

240.83(C)


400

What are the key requirements for a feeder tap that is 10 feet or less in length?

  • The tap conductors must have an ampacity of at least 10% of the rating of the overcurrent protective device (OCPD) protecting the feeder.
  • The tap conductors must be enclosed in a raceway or enclosure if they leave the enclosure where the tap is made.
  • The tap must terminate in a single circuit breaker or set of fuses.
  • Tapping a tap (stacking/secondary taps) is prohibited.
400

4000


Standard size or not ?

What size wire would be used going to this breaker ? (copper THHN 3 phase) (277/480)

500

What size wire is needed for a 225amp service ?

.

500

Define Overcurrent 

Any current in excess of the rated current of equipment or the ampacity of a conductor. It may result from overload, short circuit, or ground fault.

500

Transformer secondary conductors 15 ft long with no secondary OCP.

❌ Violation unless meeting 240.21(C)(6)(1-3)

NEC Reference

240.21(C)


Ampacity of the secondary conductors, to meet this rule, must not be less than:


(Primary voltage/ Secondary voltage) x 1/3 Primary OCPD.  For example: 480v primary, 208 secondary, 100 OCPD.

(480/208) x 33.33 = 77 Amps

500

What are the core conditions for a 25-foot feeder tap?

  • The tap conductors must have an ampacity of at least one-third (1/3) of the rating of the overcurrent device protecting the feeder.
  • The tap conductors must be suitably protected from physical damage (e.g., inside a raceway).
  • The total length of the tap conductor must not exceed 25 feet.
  • The tap terminates in a single circuit breaker or set of fuses rated no more than the tap conductor's ampacity. [1, 2]
500

3050


Standard size or no ? 

NO. What size breaker and wire would you use if this was the amperage of the equipment you are feeding ? 