Dwelling Units
Conduit
Swimming Pools, fountains, and similar installations
100

Bathrooms, Outdoors, Basements and Kitchen receptacles must be protected with this device.

GFCI

Article 210.8(A) (1-12)

100

This is the total degrees of bends allowed within a run in between pull points.

360 degrees

Artilce 358.24(B)

100

An area including a sink with one or more of the following: a toilet, urinal, tub, shower or bidet.

Bathroom

Article 100

200

This is the distance where receptacles are installed within the outside edge of the bathtub or shower stall that are required to be GFCI protected.

6'

Aritcle 210.8(A)(7)

200

Rigid Polyvinyl Chloride Conduit shall be securely fastened withing ____feet of an outlet box.

3'

Article 352.30(A)

200

a compartment or chamber to which one or more air ducts are connected and that forms part of the air distribution system.

Plenum

Article 100

300

This is the branch circuit rating for a bathroom.

20 Amp

210. 11(C)(3)

300

This is the maximum distance between Rigid Metal Conduit supports (in straight runs) of 2".

16'

Table 344.30(B)

300

Rendered inaccessible by the structure or finish of the building.

concealed

Article 100

400
This is the maximum distance above a countertop or work surface for a receptacle installation.

20"

Article 210.52(C)(3)

400

Flexible Metal Conduit trade size 1/2" shall not be used in lengths not in excess of ______ for utilization of equipment.

6'

Article 348.20(A)(2)(a)

400

an enclosed channel designed expressly for holding wires, cables, or busbars, with additional functions as permitted in this code.

Raceway

Article 100

500
GFCI protection shall be provided for lighting outlets not exceeding _____ volts installed in crawl spaces.

120

Article 210.8(C)

500

LFMC is required to be supported within ____ of each box.

12"

350.30(A)

500

connected to ground or to a conductive body that extends the ground connection.

Grounded (Grounding)

Article 100