100
Hoods need to be this far away from combustible material. 

What is 18 inches?

100

This is the size of hood stickers.

5.5 X 4.25 inches

100
This is what an upblast fan must drain its grease into. 

What is a 1 gallon grease recepticle?

100

Ducts can be made out of these materials. 

What is 16 MSG steel or 18 MSG stainless steel?

100

For vertical ducts that can not be entered by personnel, this is where the access panels need to be.

What is on every floor?

200
The distance a rooftop fan needs to be from any adjacent property.

What is 10 feet?

200

What the certified employee needs to legibly print on a hood sticker.

What is their name and BFD registration number?

200

Exhaust fan housings must be made out of this material.

What is 16 MSG steel or 18 MSG stainless steel?

200

A sign with these words must be placed on all access panels.

What is ACCESS PANEL - DO NOT OBSTRUCT?

200

This object is placed in or near an appliance to change the direction or slow the flow of air or flue gases. 

What is a baffle plate?

300

How far smoke and grease laden vapors need to travel around a baffle plate to a grease filter. 

What is 18 inches?

300

This is where Deficiency Reports must be kept in case the BFD wants to review them.

What is at the inspected cooking establishment?

300

This is where the belts, pulleys and motor need to be in an in-line fan.

Where is outside of the airstream in a grease tight housing?

300

This is how large enclosure access openings must be. 

What is big enough for the removal of the duct access panel through the opening?

300

The maximum temperature for an actuation device in an air plenum.

What is 286 F (141 C)?

400

Ducts need to be this far away from the interior of a non combustible enclosure.

What is 6 inches?

400

Annual stickers are this color.

What is green?

400

The required air velocity in most ducts.

What is 500 FPM?

400

The amount of weight that a horizontal duct system larger than 24 inches at a cross section must support.

What is 800 lbs plus the weight of the duct?

400

Drawings of exhaust system installation must be kept at this location.

What is the cooking establishment?

500

The distance between a grease filter and cooking equipment without exposed flame and where flue gasses bypass the grease removal devices.

What is 6 inches?

500

This information must be pre printed on hood stickers.

What is the company name, complete address and 24 hour emergency services phone number?

500

The maximum negative air pressure for a cooking area.

What is .02 inches water column?

500

The fire resistance rating of an enclosure in a 7 story building. 

What is 2 hours?

500

The maximum grease discharge for reduced emissions.

What is 5 mg/m3?