Terms/Definitions
Function and Placement
Types
Device Ratings
NEC Requirements
100

Any current in excess of the rated current of equipment or the ampacity of a conductor

What is an overcurrent?

100

The circuit conductors between the final overcurrent device protecting the circuit and the outlet(s)

What is a branch circuit?

100

Often available in class J, H, and RK1

What is a fuse?

100

A term used to describe standard physical dimensions of circuit breakers

What is frame size

100

OCPD shall be provided in each ungrounded circuit conductor and shall be located here.

What is at the point where conductors receive their supply?

240.21

200

An electrical circuit condition best described as a phase or ungrounded conductor that comes into contact with another phase conductor or grounded conductor

What is short circuit?

200

Overcurrent protection shall be provided in this type of circuit conductor

What is ungrounded?

200

Encased in a sealed insulating case with a center mounted toggle operating handle

What is molded case circuit breaker?

200

Interrupting ratings other than 10,000 must be marked on this type of OCPD

What is a fuse?

200
Maximum branch circuit current allowed for a continuous load connected to a 16 AWG copper conductor.

What is 8 amps?

240.4(D)(2)

300

A current greater than the equipment rated current or conductor ampacity, which is confined to the normal conductive paths provided by the conductors and other equipment

What is an overload?

300

Supplemental overcurrent protection devices do not provide protection for this circuit condition

What is an overload?

300

A type of fuse the is cylindrical in shape and is installed in systems up to 300 Volts

What is a cartridge fuse?

300

The highest current at rated voltage that a device is identified to interrupt under standard test conditions

What is interrupting rating?

300

Plug fuses rated at 15 amperes and less shall be identified by this shape window, cap or other prominent part to distinguish them from fuses of higher ampere ratings.

What is hexagonal?

400

The amount of current available for a short circuit condition in which there is a direct connection between the ungrounded conduductors of a circuit.

What is bolted fault current?

400
Intentional delays in OCPD opening times are sometimes designed into the system to achieve this

What is selective coordination?

400
This type of OCPD is often installed in switchgear and usually requires a racking process to engage and disengage the device into busing providing a current pathway to and from the device.

What is low voltage power circuit breaker?

400

Typically, the single most influencing factor on the magnitude of the available short-circuit current at the service

What is the service transformer?

400

Maximum length of a transformer secondary conductor if the transformer primary is fed from a feeder tap that is 10 feet in length.

What is 15 feet?

500

A graph that plots the interrupting time of an overcurrent device based on a given amount of current

What is a time current curve?

500

A category of overcurrent protection used for services, feeders, branch circuits, and equipment providing a full range of protection against short circuits, ground faults, and overloads.

What is branch circuit overcurrent protection? 

Or 

What is branch circuit?

500

An OCPD with a molded plastic frame, often installed in switchboards and requires charging of an energy storage device to close the circuit

What is an ICCB?

500

This type of circuit breaker such as 120/240V or 277/480V, is permitted on a solidly grounded system where the nominal voltage of any one conductor to ground doesn’t exceed the lower of the two values, and the nominal voltage between any two conductors doesn’t exceed the higher value.

What is slash rated?

500

A circuit breaker used on a circuit having an available fault current higher than the marked interrupting rating by being connected on the load side of an acceptable OCPD having a higher rating.

What is series rated?

M
e
n
u