Terms/Definitions
Function and Placement
Types
Device Ratings
NEC Requirements
100

Any current in excess of the rated current of equipment or the ampacity of a conductor

What is an overcurrent?

100

The circuit conductors between the final overcurrent device protecting the circuit and the outlet(s)

What is a branch circuit?

100

Often available in class J, H, and RK1

What is a fuse?

100

This is the smallest standard size fuse.

What is a 1A fuse?

100

OCPD shall be provided in each ungrounded circuit conductor and shall be located here.

What is at the point where conductors receive their supply?

240.21

200

An electrical circuit condition best described as a phase or ungrounded conductor that comes into contact with another phase conductor or grounded conductor

What is short circuit?

200

Overcurrent protection shall be provided in this type of circuit conductor

What is ungrounded?

200

Encased in a sealed insulating case with a center mounted toggle operating handle

What is molded case circuit breaker?

200

Interrupting ratings other than 10,000 must be marked on this type of OCPD

What is a fuse?

200

Maximum size OCPD allowed to protect a #10AWG THHN.

What is 30 amps?

240.4(D)

300

A current greater than the equipment rated current or conductor ampacity, which is confined to the normal conductive paths provided by the conductors and other equipment

What is an overload?

300

Supplemental overcurrent protection devices are usually installed by who?

Who is the manufacturer?

300

Fuses often come in two different AC voltage ratings, 250VAC and this.

What is 600V?

300

The highest current at rated voltage that a device is identified to interrupt under standard test conditions

What is interrupting rating?

300

Switches must have an rating indicating it is capable of safely interrupting what?

What is load current?

400

The amount of current available for a short circuit condition in which there is a direct connection between the ungrounded conduductors of a circuit.

What is bolted fault current?

400

In some breakers, as the current gets larger the opening time gets quicker, often referred to as this.

What is an inverse time circuit breaker ?

400
This type of OCPD is often installed in switchgear and usually requires a racking process to engage and disengage the device into busing providing a current pathway to and from the device.

What is low voltage power circuit breaker?

400

Typically, the single most influencing factor on the magnitude of the available short-circuit current at the service

What is the service transformer?

400

Tap conductors that are run 20' in length are going to need to have an ampacity based on both: the rating of what the tap is terminated in, and also this.

What is 1/3 of the rating of OCPD protecting the feeder?

500

A graph that plots the interrupting time of an overcurrent device based on a given amount of current

What is a time current curve?

500

A category of overcurrent protection used for services, feeders, branch circuits, and equipment providing a full range of protection against short circuits, ground faults, and overloads.

What is branch circuit overcurrent protection? 

Or 

What is branch circuit?

500

An OCPD with a molded plastic frame, often installed in switchboards and requires a ratcheting device to close the circuit, but you cannot service any of the components.

What is an ICCB?

500

This type of circuit breaker such as 120/240V or 277/480V, is permitted on a solidly grounded system where the nominal voltage of any one conductor to ground doesn’t exceed the lower of the two values, and the nominal voltage between any two conductors doesn’t exceed the higher value.

What is slash rated?

500

According to 215.4, you must be able to serve THIS load when you are sizing your conductors, after you adjust and correct.

What is the maximum load to be served?

M
e
n
u