FEEDERS
Feeder grounded conductors not connected to an overcurrent device can be sized at _____ of the continuous and noncontinuous load.
100 percent
Reference:215.2(A)(1) Ex 3x
When calculations in Article 220 result in a fraction of an ampere that is less than _____, such fractions can be dropped.
0.5
Reference:220.5(B)
In accordance with Article 225 – Outside Branch Circuits and Feeders, the disconnecting means for a building supplied by a feeder shall be installed at a(an) _____ location.
readily accessible
Reference:225.31(B)
Service conductors supplying a building or other structure shall not _____ another building or other structure.
pass through the interior of
Reference:230.3
Circuit breaker enclosures shall be permitted to be installed horizontally where the circuit breaker is installed in accordance with _______
240.81
Reference:240.33
Where dwelling units are supplied by a feeder and the distribution equipment is ____, the required Type 1 or Type 2 SPD shall be installed.
replaced
Reference:215.18(D)
For dwelling units, the calculated floor area for the general lighting load shall not include _____.
open porches
Reference:220.5(C)
Open individual conductors shall not be smaller than _____ AWG copper for spans up to 50 ft in length and _____ AWG copper for a longer span, unless supported by a messenger wire.
10, 8
Reference:225.6(A)(1)
The minimum service-entrance conductor size shall have an ampacity not less than the maximum load to be served after the application of any _____ or _____ factors.
adjustment or correction
Reference:230.42(A)(2)
Circuit breakers shall _____ all ungrounded conductors of the circuit both manually and automatically unless specifically permitted otherwise.
open
Reference:240.15(B)
Where a portion of a feeder is connected at both its supply and load ends to separately installed pressure connections in accordance with 110.14(C)(2), it shall be permitted to have an allowable ampacity _____ the sum of the continuous load plus the noncontinuous load.
not less than
Reference:215.2(A)(1) Ex 2
Nondwelling unit motors rated less than _____ and connected to a lighting circuit shall be considered general lighting load.
In accordance with Article 225 – Outside Branch Circuits and Feeders, a building or structure shall be supplied by a maximum of _____ feeder(s) or branch circuit(s), unless specifically permitted otherwise.
one
Reference:225.30.
One- and two-family dwelling emergency disconnecting means are permitted to be a listed disconnect switch or circuit breaker that is marked _____ for use as service equipment, but not marked as suitable only for use as service equipment, installed on the supply side of each service disconnect.
suitable
Reference:230.85(B)(3)
Remote access for an adjustable trip circuit breaker is permitted to be achieved by being connected through a networked interface where the circuit breaker and associated software for adjusting the settings are identified as being evaluated for _____.
cybersecurity
Reference:240.6(D)(2)(a)
Where a feeder supplies continuous loads or any combination of continuous and noncontinuous loads, the conductor ampacity shall be no less than the noncontinuous load plus _____ of the continuous load.
125 percent
Reference:215.2(A)(1)
For dwelling unit load calculations in accordance Article 220, a load of not less than _____ for the laundry branch circuit shall be applied.
1,500 VA
Reference:220.52(B)
For all other installations supplied by a feeder(s) or branch circuit(s) and not specifically identified in 225.39(A) through (C), the feeder or branch-circuit disconnecting means shall have a rating of not less than _____.
60A
Reference:225.39(D)
Overhead service conductors installed over roofs shall have a vertical clearance of not less than _____ ft above the roof surface, unless a lesser distance is permitted by an exception.
8
Reference:230.24(A)
Standard ampere ratings for circuit breakers and fuses do not include _____.
a.10A
b.35A
c.75A
d.225A
Where a premises wiring system contains feeders supplied from more than one nominal voltage system, each ungrounded conductor of a feeder shall be identified by phase or line and system by _____, ____, ______, or other approved means.
color coding
marking tape
tagging
Reference:215.12(C)(1)(a)
Under the optional method for calculating a single-family dwelling unit service, general loads beyond the initial 10 kVA are assessed at a _____ demand factor.
40 percent
Reference:220.82(B)
The emergency disconnecting means for one- and two-family dwelling units supplied by an outside feeder shall have a short-circuit current rating equal to or greater than _____.
the available fault current
Reference:225.41(A)(2)
Underground service conductors shall be protected from damage in accordance with _____ including minimum cover requirements.
300.5
Reference:230.32
Circuit breakers used to switch high-intensity discharge lighting circuits shall be listed and marked as _____.
HID
Reference:240.83(D)