Raceway Basics
EMT
Installation and Bending
PVC
RMC
100

What is a raceway used for in electrical systems?

A channel to run wire and to provide protection for that wire.

100

What tool is used to bend EMT?

Hand bender, auto bender.

100

What is the most common size EMT used in residential work?

1/2"

100

What color is electrical PVC?

Gray.

100

What does RMC stand for?

Rigid Metal Conduit.

200

Name one example of a raceway.

EMT, RMC, PVC

200

Can EMT be threaded?

No

200

What is the maximum number of bends allowed in EMT between pull points?

360 degrees.

200

Can you use white plumbing PVC for electrical installations?

No.

200

What is RMC typically made from?

Galvanized or stainless steel.

300

Is IMC thicker or thinner than RMC?

Thinner

300

What is EMT conduit made of?

Galvanized steel and aluminum.

300

What must be done to avoid damaging conductors when pulled through a raceway?

Ream or deburr the pipe.

300

What does PVC stand for?

Polyvinyl Chloride.

300

Where would RMC be a better choice than EMT or PVC?

Near the floor of an industrial facility.

400

What is the star on a hand bender used for?

The second bend in a back-to back 90

400

What NEC article covers EMT?

Article 358

400

What is the take up for a 90 degree bend with 3/4" EMT?

6"

400

What NEC article covers PVC conduit?

Article 352.

400

What NEC article governs the installation of RMC, and what key rule does it state about thread protection?

Article 344; threads must be protected from corrosion by paint tape or compound.

500

What is the difference between a raceway and a cable like Romex?

A raceway is a continuous enclosed pathway for wires. Romex is a cable assembly.

500

What should NEVER be done with galvanized metal and why?

Welding. At high temperatures, the zinc coating vaporizes and puts off toxic fumes.

500

What is the take up for a 90 degree bend using 1/2" EMT?

5"

500

What is one advantage of using PVC over metal conduit?

It is lightweight, non-corrosive, and easy to cut.

500

Why is RMC permitted to serve as an equipment grounding conductor, and what NEC condition must be met for that to be allowed?

Because it is a metal pipe and thus conductive. NEC 250.118 states that all couplings and fittings must ensure a reliable and conductive path.