Branch Circuits
Grounding & Bonding
Wiring Methods & Cables
Special Locations
100

What's the minimum number of 20 amp circuits required for a dwelling unit

4

210.11 (C) (1) (2) (3)

100

The ground ring shall be installed not less than _____ below the surface of the earth.

30 inches

250.53 (F)

100

Type MC cable shall be supported at intervals not exceeding _____ unless otherwise permitted.

6' feet

330.30 (C)

100

In category 2 spaces each patient bed location in health care facilities shall be provided with a minimum of ___ receptacles.

Eight

517.18 (B) (1)

200

The circuit conductors between the final overcurrent device protecting the circuit and the outlet(s).

Branch Circuit

Article 100

200

Grounding electrode conductors smaller than ____ shall be protected in RMC, IMC, Schedule 80 PVC, RTRC-XW, EMT, or cable armor.

6 AWG

250.64 (B) (3)

200

A #8 AWG takes up how much free space inside a box? (volume)

3.00 Cubic inches

314.16 (B) (1)

200

Portable structures shall not be located under or within a space that is located ____ horizontally and extending vertically to grade of conductors operating in excess of 600 volts.

15' feet

525.5 (B) (2)

300

The rating of any one cord-and-plug connected utilization equipment not fastened in place shall not exceed ____ of the branch circuit ampere rating.

80 percent

210.23 (B) (1)

300

A service with a size 3/0 copper ungrounded conductor requires a size _____ aluminum grounding electrode conductor 

1/0 Aluminum 

Table 250.66

300

Where the opening to an outlet, junction, or switch point is less than 8" inches in any dimension, each conductor shall be long enough to extend at least ____ outside the opening.

3" inches

300.14

300

Pool-associated motors shall be permitted to employ cord-and-plug connections. The flexible cord shall not exceed ____ in length.

3' feet

680.21 (A) (2)

400

A ____ amp branch circuit shall be permitted to supply one or more of the following: lighting outlets, dwelling unit exhaust fans on bathroom or laundry room lighting circuits, or a gas fireplace unit supplied by an individual branch circuit.

10 amp

210.23 (A)

400

If a single rod, pipe, or plate grounding electrode has a resistance to earth of _____ or less, the supplemental electrode shall not be required.

25 ohms

250.53 (A) (2) Exception

400

At every outlet used exclusively for lighting, the box shall be designed or installed so that the luminaire or lampholder can be attached. Boxes shall be required to support a luminaire weighing a minimum of ____. 

50 lbs.

314.27 (A) (2)

400
The minimum size of conductors for communications in elevators is ____.

24 AWG

620.12 (A) (2)

500

In dwelling units and motels, the voltage shall not exceed ______ volts nominal between conductors that supply the terminals of cord and plug connected loads 1440 VA nominal or less, or less than 1/4 hp.

120 volts

210.6 (A)

500

The voltage developed between the portable or mobile equipment frame and ground by the flow of maximum ground-fault current shall not exceed ___.

100 volts

250.188 (C)

500

The minimum size of conductors for voltage ratings up to and including _____ shall be 14 AWG copper or 12 AWG aluminum or copper-clad aluminum, except as permitted elsewhere in this code. 

2000 volts

310.3 (A)

500

A spot welder supplied by a 60 hertz system makes three hundred 20-cycle welds per hour. What is the duty cycle percent for this welder?

2.8%

630.31 (B) Informational note 3

300x20=6000/216,000=.0277777x100=2.77 or 2.8