Every project related email has this in the subject line
What is the project name.
:= in structured text.
What is set equal to.
This is the most common graphical mistake on the HMIs
What is Flashing switches, breakers, and alarms
This done on the 487E is the primary form of transformer protection.
What is 87 (differential protection)
Often the first stop when troubleshooting internal issues.
What is a Vendor print
Every QA has one of these.
What is a QA checksheet
The section of the RTAC used to map Source to a Destination.
What is the Tag Processor
Often the first page and most important page of the HMI displaying a full site overview matching the layout of EC-100 drawing
What is the ONELINE page.
With the Tap changer on the highside, do this to lower voltage.
What is Raise Tap.
Often used as an IO box on our Breakers
What is SEL-2505
This needs to be updated on your computer and the burner before every integration trip.
What is SEL software (compass)
If this is not passed along or not present in the originating point this needs to be forced in the Tag Processor
What is Time and Quality.
A control box for a breaker or switch should contain, 2 control buttons, a Local/Remote switch display (if applicable) and a what?
What is a SCADA Enable/Disable display
Device with most of its units being in PPM (parts per million)
What is a DGA.
The greenhouse gas in highside breakers
What is SF6
The document used to find the Band center setpoint for the Beckwith
What is reactive power study
The starting register for Holding registers in MODBUS
What is 40000.
Platform used by many vendors for HMI display that is atypical for us to program in.
What is Ignition.
The size resistor used on a M-2025B to produce a 4-20mA signal
What is 150ohm
Current is travelling from the bottom of the CT not hitting the polarity dot first, the secondary value has this sign.
What is negative.
The most important thing to be packed in a pelican for an integration trip, used often to cut things.
What is scissors
Our preferred standard DNP Variation for object 30.
(Single Precision floating point 32 bit)
What is Var 5
The type of operSPC commands used from the HMI
What is operTrip and operClose
The letter on the nameplate denoted for impedance.
What is Z
In order the Phase colors on a CT secondary circuit. A,B,C,N
Black, Red, Blue, Orange