ECT
RTU
HMI
MPT
BKR
100

Every project related email has this in the subject line 

What is the project name.

100

:= in structured text.

What is set equal to.

100

This is the most common graphical mistake on the HMIs

What is Flashing switches, breakers, and alarms

100

This done on the 487E is the primary form of transformer protection.

What is 87 (differential protection)

100

Often the first stop when troubleshooting internal issues.

What is a Vendor print 

200

Every QA has one of these.

What is a QA checksheet

200

The section of the RTAC used to map Source to a Destination.

What is the Tag Processor

200

Often the first page and most important page of the HMI displaying a full site overview matching the layout of EC-100 drawing

What is the ONELINE page.

200

With the Tap changer on the highside, do this to lower voltage.

What is Raise Tap.

200

Often used as an IO box on our Breakers

What is SEL-2505

300

This needs to be updated on your computer and the burner before every integration trip.

What is SEL software (compass) 

300

If this is not passed along or not present in the originating point this needs to be forced in the Tag Processor

What is Time and Quality.

300

A control box for a breaker or switch should contain, 2 control buttons, a Local/Remote switch display (if applicable) and a what? 

What is a SCADA Enable/Disable display

300

Device with most of its units being in PPM (parts per million)

What is a DGA.

300

The greenhouse gas in highside breakers

What is SF6

400

The document used to find the Band center setpoint for the Beckwith

What is reactive power study

400

The starting register for Holding registers in MODBUS

What is 40000.

400

Platform used by many vendors for HMI display that is atypical for us to program in.

What is Ignition.

400

The size resistor used on a M-2025B to produce a 4-20mA signal

What is 150ohm

400

Current is travelling from the bottom of the CT not hitting the polarity dot first, the secondary value has this sign.

What is negative.

500

The most important thing to be packed in a pelican for an integration trip, used often to cut things.

What is scissors

500

Our preferred standard DNP Variation for object 30.

(Single Precision floating point 32 bit)

What is Var 5

500

The type of operSPC commands used from the HMI

What is operTrip and operClose

500

The letter on the nameplate denoted for impedance.

What is Z

500

In order the Phase colors on a CT secondary circuit. A,B,C,N

Black, Red, Blue, Orange

M
e
n
u