Protection and Relays
HV Testing & Diagnostics
Switching, Safety & Systems
100

What ANSI device function is used for transformer differential protection?

87T (Transformer Differential)

100

What does PI (Polarization Index) represent in insulation resistance testing?

The ratio of 10-minute IR to 1-minute IR, used to indicate insulation condition (e.g., moisture/contamination effects and polarization behavior)

100

What is the field verification step called that confirms equipment is de-energized before applying grounds?

Test-before-touch / prove dead (verify absence of voltage)

200

A relay pickup is set to 0.30 A secondary on a 600:1 CT. What is the primary pickup current?

180 A

200

In transformer DGA, which key gas is most indicative of high-energy arcing?

Acetylene (C₂H₂)

200

A 30 MVA, 34.5 kV transformer has Z = 8% on its own base. Ignoring other sources, estimate the 3-phase symmetrical fault current at the 34.5 kV bus.

~6.275 kA

300

A biased differential uses:

Iop = |I1 - I2|; Ires = (|I1| + |I2|)/2

Trip criterion: Iop > slope * Ires

Assuming above minimum pickup, at what slope will the relay trip if I1 is 1.2 A and I2 is 0.8 A?

Slope < 0.4

300

In PF / tan-delta testing, which is typically a bigger concern: a single “acceptable” value, or trend behavior over time? Explain briefly.

Trend behavior (rate of change vs. baseline) is often more concerning; a deteriorating trend can indicate progressive insulation degradation even if the absolute value remains within limits.

300

A 30 MVA, 34.5 kV transformer has Z = 8%, estimate the available 3-phase fault level (MVA) at the 34.5kV bus (transformer-limited).

375 MVA