100


1. The efficiency of the refrigerant cycle is affected by the operation of the condenser. Of the following, a more efficient centrifugal compressor operation results from:

A: Raising the condenser liquid level to the maximum

B: Lowering the chilled water set point

C: Raising the condenser head pressure

D:Lowering the condensing pressure

D:Lowering the condensing pressure

100

2. The heat removed from the refrigerant in a condenser is:

A:Sensible and latent heat

B:Latent heat only

C:Radiant heat only

D:Sensible heat only

A:Sensible and latent heat

100

3. The refrigerant unit that you have been assigned to is being taken out of service for a major repair.You have been assigned to withdraw refrigerant for storage in suitable containers. According to the New York City fire code, you must ensure that the containers:

A:Do not weigh more than 200 pounds when filled

B:Are approved by the US Department of Transportation

C:Are approved by the OSHA Association

D:Do not exceed 55 Gallon in capacity

B:Are approved by the US Department of Transportation

100

4. Which of the following best describes how the cylinder unloader work?

A:Keep in the suction valve opened while the compressor is in the return stroke

B:Controls the clearance volume in the compressor with a solenoid

C:Controls the opening of the passage into the compressor with variable vanes

D:Unloads the piston to create less pressure

A:Keep in the suction valve opened while the compressor is in the return stroke

100

5. In most semi Hermetic compressors, the suction vapor is used to:

A:Removes oil from the motor housing

B:Cools the motor

C:Minimizes oil foaming

D:Removes oil foam from the shaft

D:Removes oil foam from the shaft

200

6. The amount of refrigerant that flows through the orifices of a economizer is determined by the:

A:Number of economizer stages

B:Temperature of the high side refrigerant

C:Number of compressor stages

D:Difference between the high side and low side pressure

D:Difference between the high side and low side pressure

200


7. The installation of an inline refrigerant cleaning system is advisable:

A:For high pressure refrigerant systems

B:To purge non-condensables

C:For systems using toxic refrigerant

D:To remove impurities from the system

D:To remove impurities from the system

200

8. The type of refrigerant system that is least likely to leak refrigerant into the building space that are being cooled:

A:The direct vented closed system

B:The direct closed system

C:Any system using reciprocating compressor

D:The indirect system

D:The indirect system

200

9. The suction pressure of a reciprocating compressor is 65 PSIG. The discharge pressure of this compressor is 120 PSIG. The atmospheric is 14.7 PSI. The compression ratio for the given condition is closest to:

A. 2.07

B. 4.41

C.1.69

D. 1.84

C.1.69

200


10. A superheated vapor is a:

A:Dry vapor at the saturation temperature

B:Dry saturated vapor

C:Dry vapor above the saturation temperature

D:Vapor with minimal amount of included liquid

C:Dry vapor above the saturation temperature

300

11. A refrigerant engineer verifies that a condenser water pump is cavitating. Of the following the most likely cause for this condition is:

A:A faulty cooling tower water level controller

B:Operating at sustaining high loads

C:Too long a period between pump servicing

D:Refrigerant leaks through the pumps packing

A:A faulty cooling tower water level controller

300

12. A centrifugal water pump is known as a lift pump when the:

A.:The pump lifts the water into the pump upon startup 

B:the water supply to the pump suction inlet is below the pump level

C:The discharge head exceed 150 feet

D:The pump is started with the suction valve open

B:the water supply to the pump suction inlet is below the pump level

300

13. A TXV is used to maintain constant:

A. Refrigerant flow

B. Evaporator pressure

C. Evaporator pressure drop

D:Evaporator superheat

D:Evaporator superheat

300

14. The chilled water supply to the building is 55F. If the chiller is being used for human comfort, should you be concerned about this, and why?

A:Yes, this temperature is too low for human comfort purpose

B:Yes, this temperature is too high for human comfort purpose

C: No, 55F is within an acceptable range

D:No, temperature gauges often give false high readings

B:Yes, this temperature is too high for human comfort purpose

300

15. The packing gland of a centrifugal pump serves to:

A:Keep the bearing cooled

B:Keeps air out of the pumps when the impeller housing is under negative pressure

C: The drip part of the packing gland gives evidence that there is water in the pump

D: All of the answers are correct

C: The drip part of the packing gland gives evidence that there is water in the pump