100

If a bus is faulted, will it ABT over?

No

100

What are the cooling methods for the transformers?

SAT has natural oil and forced air

UAT and MPT have forced oil and air

100

What is bus duct cooling cooled by?

WS

100

How do you open and close OCB and GCB?

Air to close, Spring to open (OCB)

Both spring (GCB)

100

What is the first thing to be done on a fuel tanker before unloading it?

Ground it

200

What does LBB or 86 device do?

Open the breakers on both sides of the switchyard if a breaker fails to open

200

What are the transformer cover gases?

SAT has bladder between atmosphere and oil

UAT and MPT have N2

200

What cools the field on the main generator?

H2

200

What is the purpose of the Fuller Earth Filter?

pH control

200

What must be done to diesel oil fuel before use?

It must be certified

300

What are the UAT, SAT, and MPT trips?

DONS

DONSB4

DDNOBS

300

What will actuate deluge on a transformer?

Diff. current or sudden pressure relay

300

Why must you trip the 41 device (PMG Output Breaker) when there is a lockout?

To remove generator field and protect the generator from internal faults

300

What is the steam supply for the TDFWpp?

MS <40%

MSR (A) >40%

300

How full do you feed the AF day tank?

80%, which is when the lo level alarm will turn off

400

What do we use for equipment and breaker tests?

Aux. contacts and MOC for equipment

Secondary contacts and trombone for breaker

400

What will autostart the WS pump?

Low header pressure of 80 psig

400

What are the SAC trips?

High air cooler outlet >145

High lube oil cooler outlet >140

High vibes >1.2mils

low motor current <15.6

low lube oil pressure <15 psig

400

What are the Main Steam Isolation signals?

Hi-2 Cnmt press 8.2 psig, Low steamlin press 640 psig, Hi steamline press rate 100psig/50s

400

On a SI with no UV signal from the ESF buses, what will the D/G do?

It will do a fast startup and stay running, but it will not power the ESF buses

500

What are the 250 VDC loads?

Computer Inverter, Vacuum Breaker Valve, Emer. DC ASSO pump, Emer. bearing oil DC pump, B & C TDFWpp Emer. DC oil pump

500

What will happen on a high rad on 0PR005J?

All fire and oil pumps will trip and 0OD030 and 0OD029 will close
500

What are the four purposes of the generator gas system?

Purity monitoring, Cover gas for stator tank and VCT, Provide H2, and Provide VCT

500

What happens on low NPSH for FW pp?

CD152 closes, CD157 opens, Start CD/CB standby pump and AOP, Fully open HD046

500

What is the full D/G startup sequence

0RPM (air start solenoid is energized, pneumatic protection pressurized, room fan starts)

40RPM (incomp. seq. timer relay energized)

250FAST (125VDC flash field energized)

280RPM (fuel oil trans pp start, air valves closed and lockout/reset isolated, crank fail circuit disabled, JW pp off, SX169 open, prelube and heaters off)

450SLOW (3 min wait the to 600rpm and flash field energized)

570RPM (ready to load signal, flash field deenergized)