What code article covers Receptacles?
Article 406
An insulated grounded conductor _____ or larger is permitted to be identified by a gray or white marking at its terminations at the time of installation.
4 AWG
200.6(B)(4)
What article covers Luminaires?
Article 410
What chapter covers wiring methods and materials?
Chapter 3
an AFCI receptacle, or AFCI protected by a receptacle or breaker
406.4(D)(4)
In a 4-wire Delta system with a high-leg, the phase with the higher voltage to ground shall be permanently marked with what color?
Orange
110.15
What luminaires are required to be listed?
ALL luminaires lampholders and retrofit kits
410.6
The total of bends in one run of PVC shall not be more that _____ degrees between pull points
360
352.26
In what area is a receptacle prohibited from being installed in a face-up position?
Under a sink
406.5(G)(2)
Each disconnecting means shall be legibly marked to indicate its purpose, unless _________.
located and arranged so the purpose is evident.
110.22(A)
Outdoor luminaires are permitted to be supported by trees.
TRUE or False?
TRUE
410.36(G)
At least ___inches of free conductor, where it emerges from its raceway or cable sheath, shall be left at each outlet, junction, and switch point for spllices or connection of luminaires or devices.
6
300.14
A detached garage at a dwelling unit does not require tamper resistant receptacles.
TRUE or FALSE?
FALSE
406.12(1)
All panelboards supplied by a feeder in ________, (what type of occupancy?) shall be permanently marked to indicate each device or equipment where the power originates.
in other than one or two family dwellings
408.4(B)
Name one place track lighting is not permitted to be installed.
Where likely to be subjected to physical damage
In wet or damp locations
Where subject to corrosive vapors
In storage battery rooms
In hazardous (classified) locations
Where concealed
Where extended through walls or partitions
Less than 1.5 m (5 ft) above the finished floor except where protected from physical damage or track operating at less than 30 volts rms open-circuit voltage
Where prohibited by 410.10(D)
410.151 (C)
1. LFNC (Carflex) is permitted to be used underground.
TRUE or FALSE?
2. LFNC Fittings are permitted to be used underground.
TRUE or FALSE?
TRUE - where listed for the purpose 356.10
BOTH -
Angle connectors cannot be concealed. Straight connectors can be underground 356.42
Receptacles shall not be installed within a zone of ___ft horizontally from a bathtub or shower?
3
406.9(C)
When using a black wire for a grounding conductor you must reidentify it with a green marking at every LB that conductor runs through.
TRUE or FALSE?
False
250.119(A)(1) Exception
What type of luminaire is not permitted in clothes closets?
Incandescent luminaires with open or partially enclosed lamps and pendant luminaires
410.16(B)
Under what condition can you use table 310.12 to size your service conductors or feeders?
You must meet all of the following:
- the service or feeder rated at 100-400 amps
- the conductors must supply the entire load
- for one-family dwelling, or an individual unit of a two-family or multi-family dwelling
- no adjustment or correction factors are required
310.12