When troubleshooting split air conditioning systems be sure to check voltage to:

 Both the indoor and outdoor unit

100

What should the resistance of a closed (on) switch be?

0

100

A technician reads a resistance of 540 ohms from the compressor start terminal to the shell of the compressor. What does this indicate about the compressor?


The motor is grounded.

100

When current passes through a switch, the voltage should ____.

Stay the same

100

What ratings must be checked when replacing a fuse?

When replacing fuses make sure to match all of the fuse ratings including: voltage, amperage instantaneous current rating and class.

200

 A method of measuring voltage across each component moving toward the malfunctioning load is called:

 Hopscotching.


200

What should the resistance of an open (off) switch be?

OL or infinite ohms 

200

When checking the resistance of a compressor, a technician reads OL on the meter. What does this indicate about the compressor?

An open motor.

200

Electrical components can be grouped into two large categories. Name the two categories.

Switches and loads 

200

List some things that can cause a system to lose its control voltage.

Control voltage can be out because the part of the system that houses the transformer has no line voltage, because of an issue with the transformer that supplies the control voltage, or because of a blown 24-volt fuse.

300

What is the normal control voltage for a residential air conditioner?

24 volts

300

What should be the resistance of a load?

A good load will have a measurable resistance

300

Which relay coil would have a higher resistance, a 24-volt relay coil or a 120-volt relay coil?

A 120-volt relay coil would have a higher resistance than a 24-volt relay coil. Higher voltage goes with higher resistance

300

What type of electrical components are thermostats, pressure controls, and overloads?

controls or switches 

300

What is often the first check made when nothing on the unit operates?

If the system does not operate at all, check to see that it has the correct line voltage

400

List the four steps for isolating an electrical problem

1. Line voltage to the unit

2. Control voltage

3. Voltage to the nonfunctional component

4. Circuit to the nonfunctional component

400

When there is high resistance across the contacts when they are closed:

A voltage drop will be read across the contacts

400

Which side of a transformer has a higher resistance?

The primary side

400

What procedure is used to isolate the break in a circuit?

The most effective method of locating a break in a circuit is a technique called hopscotching

400

 Most circuits put all the controls on

One side of a load.


500

When current passes through a load, the voltage should

Drop

500

With the motor leads disconnected from the circuit, a technician reads 120 ohms between a motor lead and the motor frame. What does this indicate?

The motor is shorted to the frame

500

 The resistance of ________ can accurately be predicted using Ohm's law

resistors

500

A technician sees that the contactor is closed and reads a voltage of 240 volts across the contacts from L1 to T1. What does this indicate about the condition of contactor contacts?

A voltage reading more than 0 volts but less than the full applied circuit voltage indicates bad electrical contacts in the switch.

500

The ________ is used to identify all the controls in series with the load.

 electrical schematic