Boiler/Steam/Condensate
WWTU
Demin Water
Fire/Utility Water
Cooling Tower & Air, N2
100

What is the type of AUX Boiler

Rentec D-type Boiler


100

What is the expected amount that WWTU will treat per day?

Answer: 75,000 Gallons

100

What 2 distinct water products does Demin system produce?

Answer: Soft Water and Demineralized Water

100

How many Tepid Water Tank are there?

2
100

Who is the vendor for Air Compressor

Answer: HITACHI Sulair

200

Why is Amine Injected to Boiler header

Answer: To reduce corrosion for the piping of boiler & steam condensate system

200

What does the Primary DAF’s use to separate sludge particles?

Answer: White water injected with air

200

How many hours of consumption does the Demin & Soft water Tank provide?

Answer: 8h (72,000 gallon) 6h (16,930 gallon)

200

What temperature does the immersion heater heated to

65F

200

How many Instrument Air Compressor are there?

Answer: 3

300

How is the Economizer heated

Answer: Flue gas from the Boiler firebox

300

Name 2 places where the waste water we treat comes from?

Answer:

Condensate dump from ATM flash drum condensate pump P-901206

·CIP waste from CIP pump P-921019

·PTU wastewater from PTU skim pit P-201080

·First flush stormwater/ oily water from stormwater sump pump P-631910/ oily water sump pump P-631920

·Condensate from HVAC Heaters

300

Where is the soft water and demin water is used

Answer:

Soft Water- PTU

Demin Water- Deaerator, Lean amine storage tank

300

What psi does the jockey pump start up?

146PSI

300

Why is Biocide Injected to Cooling Tower?

Answer: to control the growth of organics

400

Pressure of steam header for heating the tanks and exchangers of PTU (Degumming, PE removal etc.)

Answer: 35 PSIG 226F

400

What 4 Chemicals are use in 3-Cell FFT?

Answer: Sulfuric Acid, Polymer, Caustic and Coagulant

400

What does the conductivity measure?

●It measures the ability to pass the electric current

●Amount of minerals and dissolved solids in water

400

Working Volume of the Fire/Utilities Tank

Answer: 919,920 gallons

400

What is cooling water supply temperature?

Answer: 85F

500

What are the 4 parts of Boiler

Answer:

1.Evaporator E-901061 (Steam and Mud Drum),

2.Economizer E-901064,

3.Air preheater E-901065 and a

4.Forced draft fan B-901062

500

Why is O2 used in Aeration Tank

Answer: “Bugs”, Biological treatment of the organic matter in the wastewater’s BOD removal

500

What is reverse osmosis in RO

●Osmotic pressure is the driving force of RO and it is proportional to the ratio of TDS on each side of the semi permeable membrane

●Reduce the total amount of TDS

500

Where are Potable Water used in?
(5)

Answer:

●guard shack, control room, administration building, rail building and safety shower/ eyewash stations.

500

What is the Pressure of HP natural gas line?

Answer: 660 PSIG then it is letdown to 525PSIG with a pressure let down

M