100

In intervals of how many years is the NEC revised?



3

100


The general rule in 2023 NEC Article 406.12 is all nonlocking-type, 125- and 250-volt, 15- and 20- ampere receptacles are required to be listed as       (blank) - (blank)  for new installations in dwelling units.

Tamper-resistant

100

Generators 15-kW or smaller must have what?



GFCI protection for personnel

100

True or False: The total degree of bends for Electric Metallic Tubing shall not exceed 360° between pulling points.



True

100

True or False: Receptacle outlets are to be calculated at no less than 90 volt-amperes for each single or for each multiple receptacle on one yoke.

False
200

A device's primary function is to  (blank)  electric energy.



Control

200


What must be completely disconnected when a switching device is turned to the OFF position?




Ungrounded conductors

200

True or False: Overcurrent protective devices shall not be located in bathrooms.



True

200

Sign and outline lighting outlets shall be calculated at a minimum of how many volt-amperes?

1200

200

Per 2023 NEC Article 314.4, metal boxes shall be   (blank)   and     (blank)     .

Grounded and bonded

300

Inevitably, unused openings in electrical boxes will appear. Of the materials listed, which is recommended for use to close the unused openings?

Materials providing equivalent protection to the box wall

Cement

Sheetrock

Wood

Materials providing equivalent protection to the box wall

300

Should the ambient temperature in which 6 AWG copper conductors with THHN insulation are installed be 44°C, what would their corrected ampacities be?


65 A

300

Per 2023 NEC Article 210.52(A)(1), the maximum distance a receptacle outlet can be located from any point along a wall space in a dwelling unit is:



6 ft

300

Which standard ampere rated overcurrent protective device is permissible to be used should a circuit's load be 855A?

800 A

300

What is the general lighting demand load for a 8,500 ft2 bank?

11050 va

400

The minimum unit load for a dwelling is (blank)   va/ft2.



3

400

How many receptacles are required for an attached garage with electric power?



One

400

What is a branch circuit?

Conductors between final OCPD and outlet box

400

What is the difference in locations permitted between Type SE cable and Type USE cable?

SE: In/on buildings, Not underground

USE: Underground, Not in/ on buildings

400

What is the demand factor (%) for 5 electric clothes dryers?

85%

500

How many 20-ampere lighting branch circuits will be required for a 3,950 ft.2 dwelling?



5

500

What is the maximum OCPD rating allowed for a 12 AWG copper-clad aluminum conductor?

15 A

500

True or False: 16 AWG Copper conductors may be protected by a 15-ampere rated overcurrent protection device.

False

500

DAILY DOUBLE:

A dwelling unit is 2,750ft2. It includes one laundry circuit, two small appliance circuits, one dryer circuit, and a range rated for 5kW. What is the demand load, using the optional method, of this dwelling?

14700 VA

500

You are tasked with installing two 12/3 NM cables, one 14/2 NM cable, and 3 devices in a metal box. Two of the devices are connected to the 12 AWG conductors and one device is connected to the 14 AWG conductors. What is the minimum volume required to house all of these materials?

32.75