THE LENGTH ALONG THE CENTERLINE OF THE PIPE AND FITTINGS IS THE?
DEVELOPED LENGTH
206.0
WHAT IS THE MINIMUM HEIGHT OF A VACUUM BREAKER ON A URINAL?
6"
MAXIMUM FIXTURE UNIT LOADING ON A 2" WASTE STACK IS?
16
703.2
WHAT IS ONE FACTOR TO DETERMINE THE SIZE OF A VENT PIPE?
LENGTH, FIXTURE UNITS, SEWER SIZE
904.1
PLASTIC PIPE FOR FUEL GAS SHALL BE USED ONLY (WHERE)?
OUTSIDE UNDERGROUND
1210.1.7
A DEVICE INSTALLED IN A DRAINAGE SYSTEM TO PREVENT REVERSE FLOW IS WHAT?
BACKWATER VALVE
204.0
WHAT IS THE CLOSEST YOU CAN INSTALL PEX PIPING TO A WATER HEATER CONNECTION?
18"
604.13
THE MINIMUM SIZES FOR VERTICAL AND HORIZONTAL WASTE PIPING SHALL BE DETIRMINED FROM THE?
TOTAL FIXTURE UNITS
703.1
EXCEPT FOR ALLYS AND STREETS, HOW FAR SHALL A VENT TERMINATE FROM A LOT LINE?
3'
906.2
HORIZONTAL 1/2" STEEL FUEL PIPE SHALL BE SUPPORTED IN INTERVALS NOT TO EXCEED ?
6'
1210.3.5.1
LOWEST PORTION OF THE INSIDE OF A HORIZONTAL PIPE IS CALLED THE?
INVERT
211.0
WATER VALVES 2 1/2" AND LARGER MAY HAVE BODIES MADE OF?
CAST IRON
606.1
WHAT IS AN ACCEPTIABLE FITTING USED TO CONNECT ONE HORIZONTAL WASTE LINE TO ANOTHER HORIZONTAL WASTE LINE?
COMBINATION WYE AND 1/8 BEND
706.3
INCREASING ONE PIPE SIZE WILL ALLOW?
REMOVAL OF LENGTH LIMITATIONS
904.2
WHAT IS THE MINIMUM SIZE A TRACER WIRE GAUGE SHALL BE?
14 AWG
1210.1.7.2
STATIC PRESSURE IS PRESSURE EXISTING WITHOUT ANY FLOW
TRUE
218.0
WHAT DOES A WATER SYSTEM WITH A PRESSURE OF 110PSI REQUIRE?
STAINER AND PRESSURE REGULATOR
608.2
WHAT IS THE MAXIMUM NUMBER OF FIXTURE UNITS ALLOWED ON A 4" HORIZONTAL DRAIN LINE RAN AT 1/8" PER FOOT OF SLOPE?
173 FIXTURE UNITS
703.2
FOOTNOTE 5
COPPER TUBING SHALL NOT BE USED FOR?
CHEMICAL OR INDUSTRIAL WASTES
903.2.2
WHAT SHALL A PRESSURE REGULATOR BE PROTECTED AGAINST?
PHYSICAL DAMAGE
1208.8.3
A VENT THAT ALSO SERVES AS A DRAIN IS A?
WET VENT
225.0
WHEN BRAZING, THE ALLOYS SHALL HAVE A TEMPERATURE ABOVE?
1,000 DEGREES
605.1.1
AFTER CAULKING A LEAD JOINT IN A CAST IRON HUB, HOW LOW SHOULD THE FINISHED JOINT BE BELOW THE HUB?
1/8" BELOW
705.2.1
PARALLEL VENT STACKS ARE REQUIRED FOR DRAINAGE STACKS THAT EXTEND?
10 STORIES OR MORE
907.1
A GAS APPLIANCE REGULATOR SHALL NOT BE VENTED TO THE?
APPLIANCE FLUE OR EXHAUST SYSTEM
1208.8.5