FOR NON-DWELLING UNITS, GFCI PROTECTION SHALL BE REQUIRED FOR OUTLETS LOCATED WITHIN ________ FEET OF A SINK OR BASIN?
6
SIX
A NEMA 1 RATED ENCLOSURE IS RATED FOR _______ LOCATIONS?
DRY
#14 AWG SHALL BE PROTECTED BY A MAXIMUM SIZE BREAKER OR FUSE OF ______ AMPS?
15 AMPS
GROUNDING RODS SHALL BE A MINIMUM OF ______ FEET IN LENGTH?
8 FEET
THE COLOR OF THE EQUIPMENT GROUNDING CONDUCTOR ON A COMMERCIAL PROPERTY IS ______?
GREEN
GREEN WITH YELLOW STRIPE
USUALLY NOT BARE
BRANCH CIRCUITS SUPPLYING INTERIOR LIGHTING CIRCUITS IN COMMERCIAL BUILDINGS ARE RATED ______ AMPS?
20 AMPS
TWENTY AMPS
A NEMA 3R RATED ENCLOSURE IS RATED FOR ______ LOCATION?
WET
WHICH AMPERE RATING LISTED BELOW IS NOT A STANDARD OVERCURRENT PROTECTIVE DEVICE SIZE?
35 AMPS
450 AMPS
601 AMPS
550 AMPS
550 AMPS
A CONCRETE ENCASED ELECTRODE IS REFERRED TO AS A ________ ?
UFER
AFCI IS AN ABBREVIATION FOR WHAT?
ARC FAULT CIRCUIT INTERRUPTER
A _______ IS A POINT ON A CIRCUIT WHERE CURRENT IS TAKEN TO SUPPLY UTILIZATION EQUIPMENT?
OUTLET
A CIRCUIT CONDUCTOR THAT IS INTENTIONALLY GROUNDED IS A ________?
GROUNDED CONDUCTOR
NEUTRAL
USING THE 10 FOOT TAP RULE, THE TAP CONDUCTORS SHALL BE NO LESS THAN ________% THE AMPACITY OF THE CIRCUIT BREAKER FEEDING THE CIRCUIT.
10%
ONE-TENTH
WHEN A BRANCH CIRCUIT EXPERIANCES A SHORT CIRCUIT TO GROUND, THE FAULT CURRENT TRAVELS ALONG THE ____________ CONDUCTOR?
EQUIPMENT GROUNDING CONDUCTOR
A GFCI OUTLET IS DESIGNED TO PROTECT ________?
PEOPLE
CONDUCTORS FOR BRANCH CIRCUITS ARE SIZED TO PREVENT A VOLTAGE DROP EXCEEDING ______%
3%
DEVICES WITH SCREW SHELLS SHALL HAVE THE _________ CONDUCTOR CONNECTED TO THE SCREW SHELL?
GROUNDED
NEUTRAL
CIRCUIT BREAKERS AND SWITCHES CONTAINING FUSES SHALL BE READILY ACCESSIBLE AND INSTALLED SO THAT THE CENTER OF THE GRIP OF THE OPERARTING HANDLE ISN'T MORE THAN ________ FT _______ INCHES ABOVE THE FLOOR OR WORKING PLATFORM.
6 FEET 7 INCHES
EACH PERMAENTLY INSTALLED SWIMMING POOL SHALL HAVE A RECEPTACLE OUTLET INSTALLED NOT LESS THAN ______ FEET AND NO MORE THAN ______ FEET FROM THE INSIDE EDGE OF THE POOL?
6 FEET
20 FEET
680.22 (A)1
THE INTENTIONALLY GROUNDED CONDUCTOR SHALL BE ONE OF TWO COLORS. NAME BOTH.
WHITE
GREY
THE MAXIMUM CORD-AND-PLUG CONNECTED LOAD ON A 20 AMP CIRCUIT WITH A 20 AMP RECEPTACLE IS ______ AMPS?
16 AMPS
A 50KVA 1-PHASE TRANSFORMER WITH A 4:1 RATIO AND 480 VOLTS PRIMARY VOLTAGE HAS A SECONDARY VOLTAGE OF ______?
120 VOLTS
WHEN OVERCURRENT PROTECTION DEVICES ARE OVER 800 AMPS, THE CONDUCTORS USED TO SUPPLY IT MUST HAVE AN AMPACITY EQUAL TO OR GREATER THAN THE _______?
OVERCURRENT PROTECTIVE DEVICE
CIRCUIT BREAKER
FUSE
A SWIMMING POOL SHALL HAVE A MINIMUM SIZE # ____ EQUIPOTENTIAL BONDING CONDUCTOR TO BOND ALL METAL PARTS OF THE POOL.
#8
680.26(B)
WHEN THE FAULT CURRENT REACHES THE MAIN DISCONNECT, IT PASSES THROUGH THE ________________ AND TRAVELS ALONG THE SYSTEM NEUTRAL CONDUCTOR TO THE GROUNDING ELECTRODE SYSTEM?
MAIN BONDING JUMPER