Circuit Breaker Troubleshooting
Group Operated Disconnects
Network Protector Basics

Infrared Temperature Analysis

Transformer Oil Analysis


100

How long should you apply HV across the terminals of the interrupter be when testing vacuum loss?

What is one minute.

100

At what amps are disconnect switch whips designed to interrupt

What is less than 12 amps.

100

The network protector has an operating handle with these three operating positions:

What are automatic, open, and close.

100

If possible, how often should infrared analysis be conducted on equipment that is energized under full load. 

What is annually.

100

Name 3 functions that oil performs in a transformer.

What are:

Provides excellent insulation

Provides cooling

High dielectric strength (the breakdown voltage)

High flashpoint and very stable at high temperatures

Oil also acts a barrier between atmospheric oxygen and the cellulose  

 

200

72% of major circuit breaker failures are directly related to these two failures.

What are drive mechanism and electrical control and auxiliary circuits.

200

switches will have adequate contact pressure if the blade has rotated to within _____________ of perpendicular in the contact.


What is plus or minus 5 degrees.

200

The network protector is designed to protect the system from:  

What are primary feeder faults and internal transformer faults..

200

90% of bushing failures are attributed to this. 

What is water entrance through the top seal.

200

What gas is an indicator of arcing/sparking and severe overheating.

What is acetylene.

300

This performs three functions: charge the closing spring, release the open spring, and release the closing spring on command.

What is the control scheme.

300

A group of vertically mounted disconnect switches are considered properly open at.

 

What is 90 degrees + to be used as a held point of clearance for workers.


300

The most important elements of an A/C network power system are the:

What are networks transformers and network protectors.

300

The temperature of a normal LTC should be __________ than the main transformer?

What is cooler.

300

What gas suggest ingress of outside air into the transformer tank.

What is oxygen.


400

If the electrical control scheme is proven operational, the next step is to troubleshoot the?

What is the mechanical portion of the mechanism.

400

The operating mechanism is intended to fully open and fully close the disconnect switch by rotating the vertical operating pipe

What is180 degrees (plus or minus)

400

Low current arcing faults on ___________________  can sustain themselves for extended periods of time and cause extensive damage, more so than at 208Y/120-volts.

What are 480/277-volt spot network secondaries.

400

If after checking the transformer oil pumps for vibration and the bearings are suspect, what should be done?

What is have the DGA lab check for dissolved metals in the oil.

400

On newly energized transformers, oil samples (DGA) are taken at what intervals. 

What is 1hr, 24hr, 48hr, 72hr, 1 week, 1 month, then once annually. 

500

Circuit breakers are designed to satisfy predetermined breaking conditions and have electrical properties that can be resumed by the following:

What are:

Current carrying property

Insulating property

Current breaking property

500

Name the three standard types of group operated disconnect switch operating mechanisms.

What are the swing handle, hand crank, and the motor operated device (MOD)


500

Radial, loop, and network are three basic types of this. 

What are distribution system designs.

500

A cool transformer radiator or segment indicates what?

What is a valve is closed or the radiator or segment  is plugged.

500

What five forms can water exist in a transformer.

1. Free water, at the bottom of the tank. 

2. Ice at the tank bottom. 

3. Water can be in the form of a water/oil emulsion. 

4. Water can be dissolved in the oil and is given in ppm in the DGA. 

5. Water can be in the form of humidity.