WHAT AREAS ARE SERVED BY THE WET PIPE SYSTEM?
CORRIDORS, FOH/BOH ADMIN, BOTH FLOORS.
ASIDE FROM THE LOW ODOR SMELL, WHAT OTHER INDICATION IS THERE THAT NOVEC 1230 GAS HAS DISPERSED?
VOICE BECOMES DEEPER.
WHAT FIRE PANEL REMOTE ANNUNCIATOR WILL THE FIRE DEPARTMENT USE WHEN RESPONDING TO A FIRE
LOBBY
WHAT ARE THE 4 ALARM INDICATIONS FROM OUR FIRE CONTROL PANELS
1. ALARM (FIRE)
2. SUPERVISORY
3. SECURITY
4. TROUBLE
WHAT ARE THE TWO CAL SUITES THAT COT'S WILL UTILIZE
12 AND 40 CAL
WHAT POSITION SHOULD YOU FIND BOTH BYPASS VALVES FOR THE FIRE PUMP?
OPEN
THIS IS A KEYLIGHT DOCUMENT THAT DISPLAYS WHAT INFORMATION
Energized Electrical Work Permit
Decision Tree
IN THE CASE OF AN ELECTRICAL FIRE WHAT IS THE IMMEDIATE RESPONSE THAT IS REQUIRED OF THE COT
SECURE POWER TO THE MALFUNCTIONING EQUIPMENT
WHEN IT COMES TO THE PODS WHAT DOES FACOPS CHECK FOR SO AS TO PREVENT A FIRE
OVERHEATING OF THE UPS BATTERIES
WHEN SWITCHING A BREAKER FROM ANY POSITION WHY MUST THE COT LOOK AWAY FROM THE BREAKER
BREAKERS ARE UNTESTED, AND IN CASE OF AN ARC FLASH
WHAT IS THE PRESSURE THAT THE JOCKEY PUMP NEEDS IN ORDER TO AUTOMATICALLY START?
145 PSI
WHAT IS "LIMITED APPROACH BOUNDARY"
THE DISTANCE FROM AN EXPOSED ELECTRICAL SOURCE WHERE A SHOCK HAZARD EXISTS
WHAT IS THE ROLE OF FACOPS DURING A REAL FIRE/ OR A FIRE DRILL
IDENTIFY THE LOCATION OF THE FIRE, AND ENSURE ALL PERSONNEL ARE OUT OF THE BUILDING
AAT THE RIC3 SITE IN THE FACOPS OFFICES 2 DIFFERENT TYPES OF FIRE PANELS ARE USED, WHAT ARE THEY
SIEMENS AND HONEYWELL
WHAT DOES A COT NEED TO HAVE PRIOR TO WORKING ON EQUIPMENT OVER 50V
EXEMPTION OR AN ENERGIZED ELECTRICAL WORK PERMIT SIGNED BY EXECUTIVE LEADER FOR THE SITE
WHAT DOES THIS PICTURE DISPLAY?
EGRESS ROUTES FOR THE SECOND FLOOR
WHEN IS A HOT WORK PERMIT REQUIRED
ANY TYPE OF MAINTENANCE THAT WOULD REQUIRE AN OPEN FLAME, OR A HEAT SOURCE
WHAT DOES THIS PICTURE PORTRAY?
OVERALL FIRE PROTECTION PLANS/ZONES
WHILE A COT IS DOING ROUNDS WHAT CAN THEY UTILIZE TO IDENTIFY A FIRE OR A RISK OF A FIRE WHILE BEING AWAY FROM AVEVA/IGNITION MONITORING SYSTEM
SIGHT, SMELL, SMOKE, RADIATING HEAT FROM A DOOR, AMBIENT TEMPERATURE
WHEN APPROACHING AN ELECTRICAL COMPONENT, YOU GO THROUGH SEVERAL STEPS TO ENSURE SAFETY WHAT ARE THEY
UTILIZE PPE, USE A HOT-STICK, ARC FLASH BOUNDRIES, LIVE-DEAD-LIVE
UPON THE RECEPTION OF A _________, THE PRE-ACTION SYSTEM ACTUATES VIA A _________ AND PRESSURIZE THE DOWNSTREAM PIPING.
FIRE ALARM.
SOLENOID/VALVE
WHAT CHECKS DO YOU PERFORM PRIOR TO UTILIZING A FIRE EXTRINGUISHER
SERVICED DATE, PRESSURE IN THE GREEN, PIN NOT BENT AND PRESENT
LOCATED IN THE BOH WHAT AREAS DO THE HIGHLIGHTED PIPES COVER IN
1-PA-1-07 : DH 1300 EAST
1-PA-1-06: DH 1200 WEST
YOU ARE A NIGHTSHIFT COT IN THE FACOPS OFFICE, AND YOU HAVE A SECURITY GUARD COME INTO THE OFFICE SOAKING WET INFORMING YOU THAT A SPRINKLER IN THE CUSTOMER CAFETERIA IS SPEWING WATER, WITH NO INDICATION OF AN ACTUAL FIRE. WHAT DO YOU NEED TO DO TO AS THE COT PREVENT FURTHER DAMAGE
VERIFY THAT THERE IS NO ACTUAL FIRE, AND THEN GO TO THE PROPER WET PIPE SYSTEM AND ISOLATE THE PIPE BY SHUTTING THE FLOW OF WATER,AND INFORM LEADERSHIP. START M.I DOCUMENTATION
WHAT ELECTRICAL TASKS DO NOT REQUIRE AN ENERGIZED ELECTRICAL WORK PERMIT? (NAME TWO)
DIAGNOSTIC TESTING, CIRCUIT IDENTIFICATION, TROUBLESHOOTING, SWITCHES, VISUAL INSPECTION, DC BATTERY CABINET ROUTINE INSPACETIONS AND MAINTENANCE, AND IR SCAN THAT DO NOT ENTER APPROACH BOUNDARY