100

OZONE CONSISTS OF MOLECULES CONTAINING (BLANK).

3 oxygen atoms

100

THERE'S NO SUCH THING AS A (BLANK) SUBSTITUTE.

drop in

100

A DEEP VACUUM IS MEASURED IN (BLANK).

Microns

100

THE SYSTEM SHOULD BE CHECKED FOR LEAKS IF THE PRESSURE IN A SYSTEM RISES FROM (BLANK) TO A LEVEL ABOVE (BLANK).

1mm hg, 2.5mm hg

100

 THE APPLICABLE MAXIMUM LEAK RATES ARE 10% FOR (BLANK), 20% FOR (BLANK), AND 30% FOR (BLANK)

comfort, commercial, and industrial

200

(BLANK) REMOVE REFRIGERANTS WITHOUT THE ASSISTANCE OF THE APPLIANCE.

self contained recovery device

200

(BLANK) IS A VERY HIGH PRESSURE REFRIERANT AND GENERALLY DOES NOT NEED TO BE RECOVERED.

carbon dioxide

200

(BLANK) IS THE EASIEST WAY TO CHECK THE TYPE OF REFRIGERANT USED.

nameplate

200

ALL PRESSURE RELIEF VALVES SHOULD PIPED OR INSTALLED IN (BLANK), NEVER (BLANK). 

parallel, series

200

 THE US IS PART OF THE (BLANK) WHICH IS A INTERNATIONAL TREATY THAT ADDRESSES OZONE DEPLETION.

MONTREAL PROTOCOL

300

SECTION 608 OF THE (BLANK) SETS FORTH THE RULES AND REGULATIONS FOR REFRIERANTS.

Clean Air Act

300

 SELF CONTAINED RECOVERY DEVICES MUST BE ABLE TO RECOVER (BLANK) OF THE REFRIGERANT WHEN THE COMPRESSOR IS OPERATING.

 90%

300

WHEN FIRST INSPECTS AN OPERATING HERMETIC SYSTEM KNOWN TO BE LEAKING, YOU SHOULD (BLANK).

search for traces of oil

300

THE USE OF A OVERSIZED VACUUM COULD CAUSE (BLANK)

 freezing the trapped water

300

THE COMPOUND GAUGE MEASURES SYSTEM PRESSURE FOR THE (BLANK) IN POUNDS PER SQUARE INCH GAUGE (PSIG).

low side

400

UPON COMPLETION OF A LEAK REPAIR, BEFORE RECHARGING THE SYSTEM, INSTALL A NEW (BLANK), AND COMPLETE A STANDING PRESSURE LEAK CHECK.

filter drier

400

WHEN USING NITROGEN, YOU MUST HAVE (BLANK) ON THE NITROGEN TANK.

regulator

400

AFTER ASSEMBLY, THE UNIT SHOULD BE PRESSURIZED WITH (BLANK)

nitrogen

400

BEFORE DISPOSING A LOW PRESSURE APPLIANCE, THE REFRIGERANT MUST BE RECOVERED TO (BLANK)

25 mm HG of absolute

400

A MEDIUM PRESSURE APPLIANCE WITH A FULL CHARGE WITH OR MORE THAN 200 POUNDS MUST BE RECOVERED TO A VACUUM OF (BLANK)

15 HG

500

 (BLANK) REFRIGERANTS MIXTURES ARE MIXTURES OF COMPONENTS THAT HAVE DIFFERENT BOILING POINTS.

zeotropic and non-azeotropic

500

IF A TECH SUSPECTS CONTAMINATION IN HIS RECOVERY CYLINDER, A (BLANK) SHOULD BE TAKEN AND COMPARED TO THE (BLANK)

pressure measurement, PT chart

500

IF THE SYSTEM OPERATES WITH EXCESSIVE SUPERHEAT, THEN A LEAK IN THE (BLANK) IS SUSPECTED.

high pressure capillary tube system

500

 EXCESSIVE RUNNING OF THE (BLANK) ON A LOW PRESSURE CHILLER GENERALLY INDICATES A LEAKING SYSTEM.

purge unit

500

YOU CAN BE FINED (BLANK) PER DAY, PER VIOLATION, FOR VIOLATING THE CLEAN AIR ACT.

44,539$