1
2
3
4
5
100

Aluminum wire expands and contracts to a greater degree than does copper wire for an equal load. This is referred to as elongation 

what is F

100

nonmetallic sheathed cable may be run exposed or concealed or concealed in dry locations T/F

what is true 

100

To make voltage drop and conductor sizing calculations for a 3-phase system, substitute the factor of 2.732 in the place of the factor 2 in the voltage drop formula T/F

what is F 

100

10,15,20 amperes rated branch circuits serve more than one outlet in usual dwelling T/F

what is T

100

Exception 1 to 312.5(c) requires that each cable is fastened within 10 inches measured along the sheath, of the outer end of the raceway 

what is F

200

Voltage drop in a residence can be observed when motors run how?

what is slower and hotter 

200

the surface of aluminum does what as soon as it is exposed to air 

what is oxidizes 

200

A simple formula for calculating voltage drop on single phase systems considers what 

what is resistance, amp rating and length of the wire

200

terminations for all electrical connections to devices and equipment are required to be tightened to the torque as required by who

what is manufacturer 

200

Nonmetallic sheathed cables are usually secured to a panelboard, box, or cabinet with what 

what is clamps or connectors 

300

the ampacity values in the tables are valid where there are no more than how many current carrying conductors in a raceway or cable and where the temperature does not exceed 86 F  

what is Three (3) 

300

Cables may feed surface mounted enclosures. where cable is used, each cable shall be secured to what

What is cabinet, cutout box, or meter socket enclosure 

300

the current-carrying capacity of copper wire for a given size, insulation , and temperature OF 30 C is rated how compared to aluminum   

what is more that of aluminum 

300

the ampere rating of the branch circuit overcurrent protective device determines the rating of what  

what is the branch circuit 

300

ampacity value depends on the conductors cross-sectional area, whether the conductor is copper, copper-clad, aluminum and what?

what is insulation 

400

even though conductors are sometimes rated higher, NEC 240.4 D spells out the maximum overcurrent protection for small branch circuit conductors. that section limits 14 AWG copper to what  

what is 15 amp overcurrent device 

400

Aluminum conductors have a higher resistance compared to copper conductors of same size. when considering what a conductors resistance is a key ingredient. 

what is voltage drop 

400

what is the maximum overcurrent protection for 12 AWG copper conductors is what 

what is 20 amp 

400

For branch circuits the recommended maximum voltage drop is what 

what is 3% 

400

for feeders the recommended maximum voltage drop is what 

what is 3% 

500

when both branch circuit and feeders are involved, the total voltage drop should not exceed what %

what is 5%

500

connectors not marked AL or AL/CU are for use with what kind of conductor 

what is copper conductor 

500

If the ambient temperature exceeds what, the ampacity values must also be corrected 

what is 86F (30 C) 

500

Circuits must be protected against overcurrent by what or circuit brakers rated not more than the ampacity of the conductors  

what are fuses 

500

312.5 C exceptions allows cables with nonmetallic sheaths to enter the top of a surface mounted enclosure through one or more nonflexible raceways not less than how many inches and no more than how many ft under certain conditions  

what is 3 inches and 10 feet