100

This grounding electrode must be used if present in a building and in contact with earth for at least 10 feet.

What is a metal underground water pipe electrode?

NEC Location: 250.52(A)(1)

100

A 4″ square metal box (1½″ deep) contains:

  • (3) 12 AWG current-carrying conductors

  • (1) 12 AWG equipment grounding conductor

  • (1) internal clamp

  • (1) device yoke with a single receptacle

Is the box large enough?

Answer: B – No

Calculation:

  • Conductors: 3 × 2.25 = 6.75 in³

  • Grounds: 1 × 2.25 = 2.25 in³

  • Clamp: 1 × 2.25 = 2.25 in³

  • Device yoke: 2 × 2.25 = 4.50 in³

Total required = 15.75 in³

Box volume (Table 314.16(A)) = 15.5 in³

👉 Not sufficient.

100

A 3 HP, 230V, single-phase motor has a full-load current of 12 A. What is the minimum size overcurrent protection device (OCPD) allowed?

 18 A

Calculation / Notes:

  • NEC Table 430.248: 3 HP, 230V, 1Ø → FLC = 12 A

  • OCPD max = 250% for short-circuit protection not allowed, normally 125% for overload → 12 × 125% = 15 A

  • Use next standard breaker size → 18 A

100

A new residential swimming pool requires bonding of all metal parts. Which of the following must be bonded?

A. Only the pool structure
B. Pool structure, metal piping, and pool lights
C. Pool deck only
D. Only underwater lights

B – Pool structure, metal piping, and pool lights

NEC References: 680.26(A), 680.26(B)

100

Which of the following defines a Class I, Division 1 location?

A. Location where flammable gases or vapors are not normally present
B. Location where flammable gases or vapors may exist under normal operating conditions
C. Location with combustible dusts
D. Location with ignitable fibers

 B – Location where flammable gases or vapors may exist under normal operating conditions

NEC Reference: 500.5(A)

200

This is the minimum spacing required between two ground rods used as electrodes.

What is 6 feet?

NEC Location: 250.53(A)(3)

200

A box contains:

  • (6) 14 AWG conductors

  • (1) 14 AWG equipment grounding conductor

  • No devices, no clamps

Minimum box volume required?

A. 12 in³
B. 14 in³
C. 16 in³
D. 18 in³

Answer: B – 14 in³

Calculation:

  • Conductors: 6 × 2.0 = 12.0 in³

  • Grounds: 1 × 2.0 = 2.0 in³

Total = 14 in³

200

A 5 HP, 460V, 3-phase motor is connected to a branch circuit. What is the minimum conductor size (AWG) for THHN copper, 75°C insulation?

#8

Calculation / Notes:

  • Table 430.248: FLC ≈ 6.9 A for 5 HP, 460V, 3Ø

  • Branch-circuit conductors must be ≥ FLC × 125% → 6.9 × 1.25 ≈ 8.6 A

  • #8 Cu → 55A (75°C) → OK

200

A 20-foot by 40-foot pool is installed in a backyard. What is the minimum distance for receptacles from the pool edge?

A. 3 ft
B. 6 ft
C. 10 ft
D. 12 ft

B – 6 ft

NEC References: 680.22(A)(1), 680.22(A)(2)

200

A facility handles finely divided grain dust that may ignite. Which classification applies?

A. Class I, Division 2
B. Class II, Division 1
C. Class III, Division 1
D. Class I, Zone 0

 B – Class II, Division 1

NEC Reference: 502.10(A)

300

This conductor connects the grounded service conductor to the equipment grounding conductors and enclosure at the service.

What is the main bonding jumper?

NEC Location: 250.28

300

A single-gang plastic box is marked 18 in³ and contains:

  • (2) 12 AWG cables entering (4 conductors total)

  • (1) switch on a yoke

  • Grounds present
    Is the box compliant?

Answer: A – Yes

Calculation:

  • Conductors: 4 × 2.25 = 9.0 in³

  • Grounds: 1 × 2.25 = 2.25 in³

  • Switch yoke: 2 × 2.25 = 4.50 in³

Total = 15.75 in³

Box volume = 18 in³

300

A motor requires 25 A at full load. What is the maximum size of the overload protection (continuous) in amperes?

35A

Calculation / Notes:

  • FLC = 25 A

  • OCPD sizing per 430.32(A) → 125% × FLC = 25 × 1.25 = 31.25 → next standard breaker size 35 A

NEC References: 430.32(A), 430.52

300

Which of the following requires GFCI protection in a pool area?

A. Outdoor lighting within 20 ft of the pool
B. Pool pump motor
C. Receptacles within 20 ft of pool
D. All of the above

 D – All of the above

NEC References: 680.22, 680.21(A), 680.22(B)

300

Class III locations include which of the following?

A. Locations with flammable gases
B. Locations with combustible dusts
C. Locations with easily ignitable fibers or flyings not likely to be in suspension
D. Locations with conductive liquids

C – Locations with easily ignitable fibers or flyings not likely to be in suspension

NEC Reference: 503.2

400

This table is used to size the grounding electrode conductor based on the largest ungrounded service conductor.

What is Table 250.66?

NEC Location: 250.66

400

A box contains:

  • (5) 10 AWG conductors

  • (1) internal clamp

  • No devices
    Required minimum volume?

Answer: D – 21 in³

Calculation:
10 AWG allowance = 2.50 in³ each

  • Conductors: 5 × 2.50 = 12.5 in³

  • Clamp: 1 × 2.50 = 2.5 in³

Total = 15.0 in³

👉 BUT PSI trap: box must be equal or greater than required.
Closest compliant standard size ≥15 in³ is typically 21 in³

400

Which of the following statements is correct about a motor branch circuit supplying a 7.5 HP, 230V, 3-phase motor?

A. OCPD must not exceed 100% of FLC
B. Motor conductor ampacity must be at least 125% of FLC
C. Motor overload protection is optional
D. Conductor ampacity can be less than FLC

 B – Motor conductor ampacity must be at least 125% of FLC

NEC References: 430.22(A), 430.32(A), Table 430.248

400

An elevator is installed in a commercial building. The NEC requires that the power circuit supplying the elevator be:

A. Fed from a dedicated branch circuit
B. Fed from the nearest lighting panel
C. On a multi-purpose circuit
D. Only grounded at the elevator motor

: A – Fed from a dedicated branch circuit

NEC References: 620.11(A), 620.51

400

n a Class I, Division 2 location, which of the following is allowed without explosion-proof equipment?

A. Ordinary branch-circuit receptacles
B. Motors rated for Division 1
C. Equipment approved for Division 2 only
D. None of the above

 C – Equipment approved for Division 2 only

NEC Reference: 504.5(C)

500

This rule requires normally non-current-carrying metal parts of equipment to be connected together and to the supply system grounded conductor.

What is equipment bonding?

NEC Location: 250.4(A)(3) & 250.110

500

A box contains:

  • (3) 12 AWG conductors

  • (2) 12 AWG conductors that pass through unbroken

  • (1) receptacle yoke

  • Grounds present

How many conductor equivalents must be counted?

Total = 8 conductor equivalents

500

A 10 HP, 460V, 3-phase motor operates with continuous duty. What percent of full-load current is the minimum rating for the branch-circuit OCPD?

A. 100%
B. 115%
C. 125%
D. 150%

Answer: C – 125%

Notes:

  • NEC requires branch-circuit conductors to handle 125% FLC for continuous motors

500

In a high-rise building, an elevator must be provided with emergency power. The source must:

A. Be a 120V receptacle in the machine room
B. Be capable of operating only the lowest car
C. Be supplied from the building emergency system
D. Be optional

C – Be supplied from the building emergency system

NEC References: 620.51(C), 700.10(A)

500

A storage facility is rated as Zone 1, 3-phase, 480V motors with flammable vapors present intermittently. According to the NEC, what type of overcurrent protection is required?

A. Standard OCPD with no special rating
B. OCPD rated for hazardous (explosion-proof) location
C. OCPD rated only for Class II, Division 1
D. OCPD rated for Class III

 B – OCPD rated for hazardous (explosion-proof) location

NEC Reference: 505.15(B), 500.7(C), 430.52(B)