VOLTAGE DROP
SIZING CONDUCTORS
Derating
Boxes & Fittings
Calculations
100

voltage drop equation is derived from this basic equation

ohm's law

100

a load that is expected to operate for 3 hours or more is called this

continuous load

100

Table 314.16(A) gives dimensions for standard size_______?

metal boxes

100

how much box volume allowance does a 10 AWG ground pigtail take up?

0

200

the difference between the value of the source voltage and the load voltage

voltage drop

200

the amount of current a conductor can carry is named this

AMPACITY

200

derating is done to prevent overheating and premature failure of a conductors what?

insulation

200

Conduit bodies that contain splices require __________ on the conduit body.

volume markings

200

In a single family dwelling, what is the service feeder rating (amps)  for a 1/0 Cu conductor

175A

300

Voltage drop is recommended not to exceed ____ for branch circuits

3%

300

upsizing current carrying conductors for voltage drop also requires upsizing this as well

Ground, EGC

300

computers, TVs, led drivers, as well as fluorescent electronic ballasts are considered this

non-linear loads

300

an octagon box containing a stud and a hickey will have how many additional conductors added to the volume

2

300

what is the minimum box volume for (4) 10 AWG THHN CU conductors 

10 in. ^3

400

In the voltage drop equation, a single phase equation multiplies the length by 2. three phase multiplies the length by ___

1.73 or square root of 3

400

If using 90 deg column on table 310.16, what else must you make sure is also rated for at least 90 deg in the circuit?

Terminals I.E.  breakers, stak ons, crimps, and lugs

400

Having 7-9 current carrying conductors in a raceway will require you to derate by this amount?

70%

400

A 4-square box with two receptacles installed adds __________ additional conductors to the fill allowance?

4

400

What is the ampacity for (4) 6 AWG THHW Cu installed in a wet location

52A

500

Voltage drop is proportional to the____ of conductor

resistance (length)

500

this rule sets MAXIMUM overcurrent protection limits for common small copper wires (14,12,10 AWG) to prevent overheating , overriding standard ampacity tables.

small conductor rule

500

the adjustment factor for more than 30 current carrying conductors in a metal wireway

40%

500

to size a pull box for straight pulls, you need to multiply the largest raceway by what?

8

500

what is the ampacity of (6) 12-2 MC going through sheetrock with no spacing between wires and has been caulked?

15A