Conduit to the Beyond
Exceptional Sections
I like to Move It Move It
Take it Outside
This Table is Just Right
100

Type Electrical Nonmetallic Tubing shall be securely fastened in place within 3' of each fitting or box where it terminates and no more than 3' thereafter.

362.30(A)

100

Electrical Metallic Tubing with factory threaded integral couplings complying with 358.100 shall be permitted.

358.28(B) Exception

100

The number of lighting branch circuits in mobile or manufactured homes is based on the calculations from this section.

550.12(A)

100

Exterior lights attached to emergency systems that are not required for illumination when there is sufficient daylight shall be permitted to be controlled by an automatic light-actuated device.

700.22

100

What cables can be substituted for FPLR cable?

T760.154(A)

200

The minimum radii of a bend for a 1/2" section of FMC is 12 and 1/2".

T360.42(A)

200

Splices and taps may be made within Underfloor Raceways provided the raceway is trench-style with an accessible, removable cover, and provided the splices and taps do not fill more than 75% of the raceway area.

390.56 Exception

200

Portable, cord connected electric signs are not required to be marked.

600.4(E) Exception

200

Overhead conductors for festoon lighting shall not be smaller than 12 AWG unless the conductors are supported by messenger wires.

225.6(B)

200

This table indicates which communications raceway types may or may not be used in communications buildings.

T800.154(b)

300

Each length of High Density Polyethylene Conduit shall be clearly and durably marked every 10' as required in 110.21.

353.120 MARKING

300

For solid bottom Cable Trays, the ampacity of signle conductor cables shall be determined by 310.14(B)

392.80(A)(2)(C) Exception

300

Portable audio equipment not listed for outdoor use shall be permitted only where appropriate protection of such equipment from adverse weather conditions is provided to prevent risk of fire or electric shock.

640.44

300

Type MC cable installed outside of buildings or structures or as aerial shall comply with 225.10, 396,10 and 396.12

330.10(B)(3)

300

Direct burial rated cable may be run under streets, highways, roads, alleys, driveways, and parking lots when they are buried at least 24".

T300.5(A)

400

Tubular Covered Conductors are not permitted to be used:

1. In any hazardous (classified) location except as permitted by other articles of this code

2. For the support of luminaires or other equipment

3. Where concealed by the building structure

4. Where accessible to other than qualified person(s)

369.12

400

Where a snap switch is used to control only one receptacle on a branch circuit, the switch shall be permitted to be rated not less than the rating of the receptacle.

404.14(G) Exception

400

Portable and mobile x-ray equipment shall comply with 660.20, but the manually controlled device shall be located in or on the equipment.

660.23

400

vegetation such as trees shall not be used for support of overhead conductor spans.

225.26

400

Outdoor motor fuel dispensing devices (except overhead types) shall be a Class 1 Division 2 location extending 18" above grade level, and extending 20' horizontally in all directions from the dispenser enclosure.

T514.3B(1)

500

I am adding a section onto an existing Flexible Bus System. The addition will be of a smaller size than the existing system. What do I need to do with my OCPD?

371.17(G) Add OCPD at the point where size is reduced.

500

Panelboards other than of the dead-front, externally operable type shall be permitted where accessible only to qualified persons.

408.38 Exception

500

The frames and enclosures of portable electrical equipment used within the cell line working zone shall not be grounded.

668.20(A)

500

For each dwelling unit of a multifamily dwelling where the dwelling unit is located at grade level and provided with individual exterior entrance / egress, at least one receptacle outlet readily accessible from grade and not more than 6 1/2' above grade level shall be installed at the front and back of the dwelling.

210.52(E)(2)

500

This table is for the selection of conductor ampacities on a messenger wire.

T310.20