A
B
C
D
E
100

Capable of being reached for operation, renewal, and inspection.

What is Accessible

100

True or False

The continuity of a grounded conductor shall not depend on a connection to a metallic enclosure, raceway, or cable armor.

Explain Where this is relevant in what we do 

True 200.2(B)

Landing a neutral on a ground bar at the first means of disconnect without a wire as a bonding jumper

Bonding screw can not be only means of bond for neutral (Grounded Conductor)

100

In both exposed and concealed locations, where a cable- or raceway-type wiring method is installed through bored holes in joists, rafters, or wood members, holes shall be bored so that the edge of the hole is not less than ________ from the nearest edge of the wood member.

What is 1 1/4" 300.4(A)

100

True or False

It is code compliant to run an extension through an open window or doorway 

What is false 400.12(3)

100

All electrical equipment located within _____ of the inside wall of the specified body of water is required to be bonded

What is 1.5m or 5ft 680.6(2)

200

Capable of being reached quickly for operation, renewal, or inspections without requiring those to whom ready access is requisite to take actions such as to use tools (other than keys), to climb over or under, to remove obstacles, or to resort to portable ladders, and so forth.

What is Accessible, Readily (Readily Accessible) 

200

What is the smallest size grounded conductor you can mark / identify?

What is number 4 AWG 200.6(B)

200

Where there is no objection because of weakening the building structure, in both exposed and concealed locations, cables or raceways shall be permitted to be laid in notches in wood studs, joists, rafters, or other wood members if ___________

What is where the cable or raceway at those points is protected against nails or screws by a steel plate at least 1.6 mm (1⁄16 in.) thick, and of appropriate length and width, installed to cover the area of the wiring. The steel plate shall be installed before the building finish is applied. 300.4(B)

200

If your extension chord is damaged, is it legal to splice it together and repair it?

Yes: The repair of hard-service cord and junior hard-service cord (see Trade Name column in Table 400.4) 14 AWG and larger shall be permitted if conductors are spliced in accordance with 110.14(B) and the completed splice retains the insulation, outer sheath properties, and usage characteristics of the cord being spliced. 400.13

200

A 240v pool heater with a name plate rating of 30a is to be installed at a single family dwelling in an outdoor location, what size wire and breaker is required to be ran in this situation?

#8 2 pole 40a GFCI breaker

300

An organization, office, or individual responsible for enforcing the requirements of a code or standard, or for approving equipment, materials, an installation, or a procedure

What is Authority Having Jurisdiction (AHJ) 

300

True or false

It is okay to use multiwire branch circuits as multiple individual circuits

Why or why not 

True as long as Each multiwire branch circuit is provided with a means that will simultaneously disconnect all ungrounded conductors at the point where the branch circuit originates. 210.4(B)

300
When does a raceway that enters a cabinet, box, or enclosure need a fitting or hub protecting the conductor from abrasion

Where raceways contain 4 AWG or larger 300.4(G)

300

True or False

You can use a switch to disconnect the grounded conductor (Neutral)

False 404.2(B)

300

Underground wiring is to be installed within 5' horizontally of a pool for a 240v 20a pool pump. What would have to be done to make this a code compliant installation?

The circuit would have to be ran using one of the following:
(1) Rigid metal conduit  

(2) Intermediate metal conduit

(3) Rigid polyvinyl chloride conduit

(4) Reinforced thermosetting resin conduit

(5) Jacketed Type MC cable that is listed for burial use

(6) Liquidtight flexible nonmetallic conduit listed for direct burial use

(7) Liquidtight flexible metal conduit listed for direct burial use

680.11

400

Connected to establish electrical continuity and conductivity.

What is Bonded (Bonding)

400

True Or False

In dwelling units and guest rooms or guest suites of hotels, motels, and similar occupancies, it is allowed to install 277v luminaires.

False 210.6(a)

400

Handhole enclosure covers shall have an identifying mark or logo that prominently identifies the function of the enclosure, such as “electric.” Handhole enclosure covers shall require the use of tools to open, or they shall weigh over __________.

What is 45kg or 100lbs 314.30(D)

400

Is a switch installed flush with the exterior wall of a residence required to have an in-use weather proof bubble cover installed?


No, it is only required to have a weather proof cover 404.4(B)

400

DOUBLE JEOPORDY

If a pool has a diving platform that is 15ft above the water level, and you are running an overhead service conductor, 120v nominal to ground with a bare messenger wire, above the diving platform, how high above the water will that overhead conductor have to be?

What is 27ft 480.9(A)

500

A load where the maximum current is expected to continue for 3 hours or more.

What is a Continuous Load

500

True Or False

A dishwasher requires GFCI protection

True 422.5(A)

500

True or False

Type NM Cable is permitted to be installed inside air voids in Masonry block.

What is true 334.10(A)(2)

500

Where operated vertically, is it permissible for the "up" position of a switch to be the open or "off" position 

No the up position must be the closed "on" position and it must be clearly identified 404.7

500

In outdoor pool areas, luminaires, lighting outlets, and ceiling-suspended (paddle) fans installed above the pool or the area extending _______ horizontally from the inside walls of the pool shall be installed at a height not less than _________ above the maximum water level of the pool.

What is 1.5 m (5 ft) Horizontally 1.5 m (5 ft) Vertically 680.22(B)(1)