EGCs must be connected in a manner where the disconnection or removal of a receptacle, device, or luminaire will not interrupt its electrical _______
What is continuity 250.148(B)
Name a location where HDPE conduit is NOT permitted to be installed
What is exposed, within a building, hazardous location, subject to ambient temps above 122F 353.12
A receptacle outlet shall be installed in dwelling units for every kitchen and dining area countertop space ____ inches or wider.
What is 12" 210.52(C)(1)
Contacts that are open when the coil is de-energized are referred to as
What is normally open
When working above a drywall ceiling it is best to support yourself by _____
What is standing on trusses (Something structural)
An underground metal ____ piping system shall NOT be used as a grounding electrode
What is gas
An outlet is a point on the wiring system at which ____ is taken to supply utilization equipment
What is current DEF 100
Where exposed to sunlight, nonmetallic equipment shall be _____ as sunlight resistant or shall be identified as sunlight resistant
Hint: General Requirements
What is listed 300.6(C)(1)
Due to high levels of ______, lighting contactors are often used to switch multiple lighting branch circuits with one single switch
What is inrush currents
In an inductive AC circuit, the ____ leads the ____
What is voltage & current
ELI
If rock bottom is encountered while driving a ground rod, the rod can be driven at an angle not to exceed ______ degrees or placed in a trench that is at least _____ inches deep
What is 45 degrees and 30
An explanatory note in the NEC recommends a voltage drop for both feeders and branch circuits to the farthest outlet to not exceed _____ %
What is 5 215.2 IN
Class III locations are those that are hazardous because of the presence of ______
What is easily ignitable fibers or materials producing combustible flyings 500.5(D)
To protect a motor, it should be equipped with automatic protective devices that will ___ the circuit
What is open
Before digging or performing any underground work it is best practice to _______
What is call diggers hotline
811
What size copper single supply-side bonding jumper is required for a raceway containing 3/0 AWG copper service conductors
What is #4 AWG T250.102(C)(1)
All energized equipment in fire pump rooms shall be located at least ____ inches above floor level
What is 12 695.12(D)
Outdoor mobile home disconnecting means shall be installed so the bottom of the enclosure containing the disconnecting means in not less than _____ above grade
What is 2 feet 550.32(F)
Overload relays can be classified as being either _____ or ______
What is thermal or magnetic
DAILY DOUBLE
What is the name of the test used to determine if metering equipment is functioning properly
What is live-dead-live
What size equipment bonding jumper is required for each metal raceway where the circuit conductors are protected by a 1,200A overcurrent protective device?
What is 3/0 AWG 250.102(D) T250.122
Aluminum, copper-clad aluminum, or copper conductors _____ and larger shall be permitted to be connected in parallel
What is 1/0 310.10(G)(1)
A single phase 2400 watt baseboard heater rated at 240 volts is connected to a 208 volt circuit. The expected current of the baseboard heater at 208 volts is _____
What is 8.6 amps
R=E^2/P 240^2/2400= 24 Ohms
I= E/R 208/24= 8.6 amps
If low-voltage and line-voltage cables must be placed in parallel runs, they should be separated by at least ____
What is 6 inches
The best way to avoid electrical shock is to ______ a circuit before working on it
What is de-energize