Test Procedures
Backflow Preventers
Backflow Theory
Troubleshooting
Code
RP
100

This backflow preventer may require the use of a "vertical pipe" 

What is the double check valve

100

Approved for sewer applications

What is the Air Gap

100

The unintentional reverse flow of water

What is Backflow

100

The type of relief valve discharge caused by fluctuating line pressure

What is intermittent discharge

100

The maximum number of days that test report forms are to be submitted by

What is 7 calendar days

100

The minimum buffer value

What is 3.0psi

200

The vertical pipe may be installed in this test port in step 2 of the DC test procedure

What is test port 4

200

Both check valves have a minimum value of 1.0psid 

What is the double check valve

200

Passed in 1974, amended in 1986 and 1996.

What is the Safe Drinking Water Act

200

Continuous discharge is usually caused by this fouled RP component

What is 

check valve #1

200

Testing frequencies are initial, annual, repair, and _______________

What is relocate

200

The minimum and maximum height for outdoor installations

Whats is 12" minimum and maximum of 36"

300

The backflow preventer requiring a higher value in step 1 than in step 2

What is the SVB

300

Not approved for continuous pressure

What is the atmospheric vacuum breaker 

300

System pressure greater than supply pressure

What is backpressure

300

This will cause the water level in the vertical pipe to drop is step 2 of the DC test

What is a leaking shutoff valve #2

300

The minimum distance above downstream piping for AVB's

What is 6"

300

The relief is designed to open at no less than ________psi of supply pressure

What is 2 pounds

400

Step 4 of the RP test procedure

What is the confirmed reading

400

Check valve opens first, then air inlet valve closes

What is the PVB

400

The head pressure at the bottom of a 6" pipe rising 80'

What is 34.64psi

400

This causes water to continue to flow from test port 2 in step 2 of the PVB test 

What is a leaking shut off valve #1

400

The ideal amount of air pressure in a thermal expansion tank

What is system water pressure

400

The position of the check valves and relief valve in a backpressure condition

What is check valves and relief valve are closed

500

This may cause the relief valve to leak in step 3 of the RP test procedure

What is disc compression or fouled CV2

500

Requiring 12" min and 60" maximum for indoor and outdoor installations 

What is the PVB and SVB

500

The principle describing how water pressure decreases as it flows through a constriction in piping

What is Bernouli's Principle

500

A missing or broken relief valve spring will cause the relief to do this

What is to not open

500

USC's "rated flow method" is used for these line sizes

What is 12" and larger

500

The two RP components that the buffer have in common

What is the relief valve and check valve #1