Wiring Methods #1
Wiring Methods #2
Wiring Methods #3
Wiring Methods #4
Class 1 & 2 Circuits
100

What is the term used in the CEC to describe any channel designed for holding wires, cables or bus bars?

Raceway

100

What is the term for the point in the wiring installation at which current is taken to supply utilization equipment?

Outlet

100

Which table provides the minimum bend radius for conduit and tubing?

Table 7

100

Which table lists the number of conductors determining box fill?

Table 23

12-3034

100

What table would you use to determine the allowable ampacity for insulated conductors of Class 2 circuits?

Table 57

200

Section 12 of the CEC deals with wiring methods for installations of _____ V or less.

750

12-000

200

What is the minimum thickness of concrete slab at grade level to permit raceways to be installed directly beneath it?

100mm

12-012 8)

200

The maximum number of bends in a conduit must not exceed _____ degrees.

360

12-942
200

What is the maximum number of outlets that may be installed on a 15A branch circuit in a dwelling unit where the breaker is rated for 80%?

12

8-304

200

What table would you use to determine what cables may be used for Class 1 & 2 circuits?

Table 19

300

What is the smallest size of rigid conduit that may be used in an electrical installation?

16

12-1004

300

What is the maximum spacing between the points of support for a single 16 trade size rigid PVC conduit?

0.75m 

12-1114

300

What is the maximum number of conductors that may be installed in a conduit?

200

12-910

300

When calculating box fill, 3 marettes/splice caps would be equivalent to how many insulated conductors?

1

Recall it is 1 conductor per PAIR of marettes (12-3034)

300

The overcurrent protection requirements of a Class 2 circuit can be met for a 30V circuit if the current is limited to _____ A.

100VA / 30V = 3.33A

16-200

400

What is the largest size SOLID conductor that may be pulled into conduit?

#10

12-914

400

The minimum bending radius of armored cables is _____ times the external diameter of the cable.

6

12-614

400

NMSC shall not be used where voltage between any 2 conductors exceeds _____ V.

300V

12-502

400

What is the minimum length of free conductor to be left at every outlet box?

150mm 

12-3000 6)

400

What is the maximum rating of fuse allowed for the protection of a Class 1 circuit where #16 AWG conductors extend beyond the equipment enclosure?

10A

16-104

500

If junction boxes are placed in attic spaces, what is the minimum vertical access height?

900mm

12-3014

500

What does NMWU stand for as it pertains to cables?

Non Metallic Wet Underground

500

What is the maximum number of #12 AWG, 600V, RW90XLPE stranded, unjacketed conductors in a 78 trade size EMT?

Table 10 -> 11.61mm2 per conductor

Table 9G -> assume 40% fill -> 2280.49

2280.49/11.61 = 196 conductors

500

What is the correct method of terminating aluminum conductors to binding terminal screws?

End of the conductor wrapped 3/4 around the screw in a clockwise direction.

12-118 6)

500

Name the 3 types of Class 1 circuits.

Remote control circuits, signal circuits, extra-low-voltage power circuits

16-000