Raceway, Box, and conductors
Masters ?s (double points)
100

What is the cross-sectional area in square inches for 4/0 AWG aluminum?

0.219 sq in.

100

 If an exit enclosure (stair tower) is required to be separated from the building, only electrical wiring methods serving equipment, permitted by the____ is permitted within the exit enclosure.

AHJ 

300.35

200

What size SE cable is required to supply a 9 kW electric furnace with a fan motor rated 1 kVA, each rated 240V with 75°C terminals.

What size SE cable is required to supply a 9 kW electric furnace with a fan motor rated 1 kVA, each rated 240V with 75°C terminals.

200

For large-scale PV installations (5,000 kW or more), buildings whose sole purpose is to house supply station equipment shall_____ comply with 690.12 for rapid shutdown systems.

not be required to


691.9

300

What size THW feeder is required to supply a 150A continuous load?

3/0 AWG

300

The emergency shutoff device for a fuel dispenser must simultaneously disconnect all conduc­tors of the circuit(s), including the____ conductor if any.

grounded


514.11(A)

400

What is the ampacity of fifteen 350 kcmil THWN aluminum conductors in a raceway at an ambient temperature 125°F?

84A

400

Unless otherwise permitted, wiring for ____ loads shall be kept independent from all other wiring and equipment.

emergency 


514.11(A)

500

How many #10 TW conductors are permitted in a 4 in. × 1½ in. square deep box?

8 conductors

500

A building may have more that one service if the capacity requirement exceeds______ amps at the 1,000 volts or less.

2,000


514.11(A)