Leak Investigation
Gas Combustion
Code Book
House Regulators
Meters
100

List 8 leakage test listed in the procedures leakage tests.

1.) Smell

2.) Visually Inspect

3.) Listen

4.) Soap Test

5.) Meter Test

6.) Manometer "u-gauge" Test

7.) Air Test

8.) Leak Detection Instrument (GMI)

100

The required air/gas ratio is the ratio of the volume of air required to burn 1 unit volume of Natural Gas completely without having any excess air in the combustion products.

10 cubic feet of air to 1 cubic foot of Natural Gas

100

These regulations cover systems for natural gas with an operating pressure of ____________ or less, and for LP-gas with an operating pressure of 20 psig. or less.....

101.2.2  125 pounds

100

House regulators control pressure by utilizing __________.

Spring Tension

100

What is the capacity of a 6" 250 BA meter?

What is the capacity of a 2lb 250 BA meter?


250 CFH

550 CFH


200

Grade 1

Grade 2

Grade 3

What are the grades for outside leaks

Grade 1 - A leak that is an existing or probable hazard and requires immediate repair

Grade 2 - A non-hazardous leak that should be repaired within 1 year not to exceed 15 months.

Grade 3 - A leak that is non-hazardous at time of detection and is expected to remain non-hazardous.

200

The Lower Explosive Limit (L.E.L.) and Upper Explosive Limit (U.E.L.) of Natural gas.

4 to 14% fuel to air ratio

200

What is the longest vent connector allowed for 20 inch vent?

What is 30 feet, Table 504.3.2. (page 100)

200

The house is protected by excess pressure through the ____________ 

Internal Relief

200

What is a split system meter set?

A system that utilizes both 6" or 1/4lb. pressure and 2lb. pressure.

300

Flame-resistant coveralls and GMI

What must be worn when working near blowing gas and must be used to monitor an area involved in a blowing gas situation.

300

The Heating value of Natural Gas  

1000 BTU per cubic ft

300

Appliance pipe connectors shall have an overall length not to exceed __________.

411.1.3.1  6 feet

300

The ___________ must be installed before the internal relief can function properly.

Spring Cap

300

A red meter index indicates......

A compensating index for elevated pressures

400

When a damaged main or service is discovered, these areas should be monitored until repairs are complete.

Homes/Buildings

Crawlspaces/Basements

Foundations

Storm Drains

Water Meter Boxes

Gas Service Risers

400

A blue flame occurs when...

primary air is pre-mixed with the fuel.

400

A yellow insulated copper _________ wire or other approved conductor shall be installed adjacent to underground nonmetallic piping.

404.17.3 tracer

400

1 inch above set pressure.

Lock up

400

Which is the best dial to use to check for the presence of leaks

0.5 ft3

500

Before entering a home, building or any type of structure the GMI should have been....

Powered on in a fresh air environment and set to the LEL scale.

500

How much air is required for a 40,000 BTU water heater need for complete combustion?

400 CFH of air

500

Piping systems exceeding ___________ shall be welded.

402.6 What is 5 pounds

500

A small vent regulator should be.....

Replaced

500

If the 1/2 foot hand makes on revolution in 15 seconds, what is the consumption rate?

120 cfh