What is contained in Article 100
What is definitions.
The purpose of the National Electrical Code is the practical safeguarding of persons and ? from the hazards arising from the use of electricity. With reference
What is (D) property
90.2(A)
Unguarded live parts above a working space operating at 10,000 volts, nominal, shall be maintained at elevations not less than ? . With reference.
What is (B), 9'6".
NEC Table 110.34(E)
The width of the working space in front of the electrical equipment less than 1,000 volts, nominal, or less shall be the width of the equipment or ? , whichever is greater and the work space shall permit at least a 90-degree opening of equipment doors or hinged panels. With reference
What is (B), 30"
Article 110.26(A)(2)
Article article is EMT listed in?
What is Article 358.
How many different parts are in Article 100
Permissive rules in the NEC are those that identify actions that are allowed but not required, are normally used to describe options or alternative methods, and are characterized by the use of the terms shall be permitted or ? . with reference
What is (D), Shall not be required
90.5(B)
“The circuit conductors between the final overcurrent device protecting the circuit and the outlet(s)“ is the definition for which of the following? With Reference
Answer:
What is (A), branch circuit
Article 100
Round access openings in a manhole shall not be less than ? in diameter. With reference
What is (B), 26"
Article 110.75(A)
What is the minimum radius of 1/2 greenfield. With reference
What is 12 1/2"
Table 360.24(A)
? is defined as the case or housing of apparatus, or the fence or walls surrounding an installation to prevent personnel from accidentally contacting energized parts or to protect the equipment from physical damage.
What is (C) enclosures
Which of the following units will appear first in the NEC when measurements are used? With reference
What is (B), SI units
90.9(B)
The conductors and equipment required or permitted in the NEC shall be acceptable only if ? . With reference
What is (A), approved
Article 110.2
Bare terminals of transformers, switches, motor controllers, and other equipment installed in a tunnel shall be ? to prevent accidental contact with energized parts. With reference.
What is (B), enclosed
Article 110.56
How often are you required to staple romex wiring. With reference
What is every 4 1/2' and 12" from a box.
Article 334.30
A ? is defined as an enclosure that is designed for either surface mounting or flush mounting and is provided with a frame, mat, or trim in which a swinging door or doors are or can be hung.
What is (B) cabinet
An informational note in Article 90 states that the format and language used in the Code follows guidelines established by NFPA and published in the ? .
What is (C), NEC style manual
Compliance with the NEC and proper ? result in an installation that is essentially free from hazard but not necessarily efficient, convenient, or adequate for good service or future expansion of electrical use. With reference
What is (C), maintenance
Article 90.2(B)
In an outdoor installation, under 1,000 volts, nominal, there is a requirement for a dedicated equipment space equal to the depth and width of the equipment and extending from grade to a height of ? above the equipment. With reference
What is (A), 6'
Article 110.26(E)(2)(c)
What is the legal depth for installing rigid metal conduit in the yard at a single family dwelling. With reference
What is 6"
Table 300.5(A)
A single cell or a group of cells connected together electrically in series, in parallel, or a combination of both is the definition of ? .
What is (A) battery
? information relative to the use of the NEC is provided in informative annexes and is not part of the enforceable requirements of the NEC. With reference
What is (C), nonmandatory
90.5(D)
Conductors and cables in a tunnel installation are required to be located ? the tunnel floor to protect them from physical damage. With reference
What is (A), above
Article 110.51(B)
Covers shall be over ? lbs or otherwise designed to require the use of tools to open and designed or restrained so they cannot fall into the manhole or protrude sufficiently to contact electrical conductors or equipment within the manhole. With reference
What is (B), 100
Article 110.75(D)
What is the allowable cable fill area (in inches) for three multiconductor cable in 4" solid channel cable trays for cables rated 2000 volts or less? With reference.
What is 2.1 inches square.
Table 392.22(A)(6)