Conductors for general wiring
Electrical non-metallic tubing
Liquidtight flexible conduit
100

Multiwire branch circuits shall only supply 

What are line to neutral loads

210.4(C)

100

ENT and associated fittings shall be 

What is listed

362.6

100

Information on the uses permitted for LFMC is found in

What is article 350.10

200

Receptacle outlets shall be installed so that at no point along the floor line of any wall space is more than

What is 6 feet from a receptacle outlet

210.52(A)(1)

200

ENT shall not be used 

What is in any hazardous location

362.12(1)

200

The maximum size of LFMC

What is trade size 4

250.12(B)

300

The rating of any one cord and plug connected utilization equipment not fastened in place shall not exceed

80% of the branch circuit ampere rating

210.23(A)(1)

300

The maximum size ENT to be used 

What is 2 1/2"

362.20(B)

300

Where equipment grounding is required for type LFNC

What is a separate equipment grounding conductor shall be installed in the conduit

356.60

400

Where installed in raceways, conductors  #8 AWG and larger

What is shall be stranded unless specifically permitted or required elsewhere in this code to be solid

310.3(C)

400

Outlet boxes or fittings designed for the support of luminaires and lampholders 

What is Shall be permitted to support a luminaire or lampholder

314.27(A) 

400

LFNC shall be marked at least every 2 feet, the markings shall include 

What is a type designation, and the trade size

356.120

500

The outer covering of THWN 

What is nylon jacket or equivalent

Table 310.4(A)

500

All joints between lengths of tubing and between tubing and couplings, fittings, and boxes

What is shall be by an approved method

362.48

500

Type LFNC shall be permitted to be used in 

What is exposed or concealed locations

356.10