100

All single-phase, 125 volt 15 and 20 amp rated receptacles located within _____ of the inside walls of a storable pool, storable spa, or storable hot tub shall be provided with GFCI protection.

20ft


NEC 680.32

100

What is the maximum length permitted for flexible cord used to supply an electrically operated in sink kitchen waste disposer?

36 inches


NEC 422.16 B 1 1


100

When switching luminaires with three-way and four-way switches, the switches shall be wired so that all switching is done only in the _____ conductor.

Ungrounded


NEC Table 404.2 A

100

Additional services shall be permitted for a single building or other structure sufficiently large to make two or more services necessary if permitted by ________.

special permission


NEC 230.2 B 2



100

Where raceways contain ____ or larger insulated circuit conductors and these conductors enter a raceway in a cabinet, the conductors shall be protected from abrasion by a smoothly rounded insulating surface such as a bushing. 

4 AWG


NEC 300.4 G

150

Type AC cable installed horizontally through wooden or metal framing members is considered supported and secured where such support doesn't exceed ____ intervals.

4.5 ft

NEC 320.30 C

150

For low voltage lighting systems operating at 30 volts ac or 60 volts dc or less, the output circuits of the power supply are to be rated for not more than ____ under all load conditions.

25 amps


NEC 411.3 and 4

150

For installation of resistors and reactors, a thermal barrier shall be required if the space between them and any combustible material is less than ____.

12 inches


NEC 470.11

150

The service equipment for a mobile home is not permitted to be located in or on the exterior wall of the mobile home however, the service equipment shall be located in sight and not more than _____ from the exterior wall of the mobile home it serves. 

50 ft


NEC 550.32 A

Art 100 def

150

All hydromassage bathtub metal piping systems and all grounded metal parts in contact with the circulating water associated with the bathtub shall be bonded together using a solid copper bonding jumper not small than _____.

8 AWG 

NEC 680.74 B

200

Polyvinyl chloride conduit (PVC) larger than trade size _____ shall not be used.

6 inches

NEC 352.20 B

200

Branch circuits that supply electric signs, other than neon signs, shall not be rated not to exceed _____.

20 amps 

NEC 600.5 C 2

200

According to the NEC the required burial depth of a direct burial cable run of a GFCI protected, 15-amp, 120-volt circuit, where the cable passes directly under the residential driveway is _____.

12 inches 


NEC Table 300.5 B column 4

200

Where practical, conductors of dissimilar metal shall _____ in a terminal or splicing connector

not be intermixed


NEC 110.14

200

Where conduit or tubing nipples having length not to exceed 24 inches between boxes or enclosures, the nipples shall be permitted to be filled to _____ of their total cross-sectional area. 

60%


NEC Chapter 9 Note 4


200

Underground service conductors that are not encased in concrete and are buried 18 inches or more below grade shall have their location identified by a warning ribbon placed at least ____ above the underground installation.

12 inches

NEC 300.5 D 3


200

A metal underground water pipe is permitted for use as a grounding electrode where the water pipe is in direct contact with the earth for at least _____ or more.

10ft

NEC 250.52 A 1

200

A hermetic motor-compressor that is protected against overloads by an inverse-time circuit breaker, shall be rated at not more than ____ of the motor-compressor full-load current. 

125%

NEC 440.52 A 3

200

A hazardous location where easily ignitable fibers or materials producing combustible flyings are handled, manufactured, or used, but where they are not likely to be in suspension in the air in quantities sufficient to produce ignitable mixtures is a ______ location.

Class 3 

NEC 500.5 D 1and2

200

Overhead spans of open conductors of not over 300 volts to ground shall have a clearance of not less than ____ over residential driveways.

12ft


NEC 225.18 2

500

Where abandoned communications cables are identified for future use with a tag, the tag shall be ______.

Of sufficient durability to withstand the environment involved


NEC  800.25

500

In compliance with the Code for dwelling units, at least one 15 or 20-amp, 125-volt receptacle outlet is required to be located in bathrooms within ____ of the outside edge of each sink. 

3ft

NEC 210.52 D

500

Unless approved for a higher voltage, surface nonmetallic raceways are not approved for use where the voltage is _____ or more between conductors.

300 volts

NEC 388.12 3

500

What is the maximum standard size overcurrent protection permitted for the protection of resistance-type fixed electric space heating equipment?

60 amps

NEC 424.22 B

500

When exceptions to the NEC are not a consideration, battery back-up exit luminaires of emergency systems shall receive power from _____.

the same branch circuit serving the normal lighting in the area



700.12 H I 2 3 A