Motors branch circuit devices and protection NEC 430
motor branch circuits and air conditioning and refrigeration equipment. article 440
Transformer protection Article 450
Interrupting rating: fully rated and series rated systems/equipment short-circuit protections
Selective coordination/Ground fault protection of equipment
100

_____and_____ are  the most common method's for establishing suitability for motor branch circuits.

Labeling , Listing 

100

where in article 430 can you find the requirements for determining  conductor ampacity and motor ratings?

430.6

100

when does the primary inrush of current occur in a transformer?

when it is energized

100

All OCPDS shall have a rating equal to or greater than the __________.

Available Fault Current

100

OCPDs must selectively coordinate for the _____ over currents possible for the application.

full range of

200

Overcurrent protection for motor circuits can be broken into two parts: motor and branch-circuit overload protection and motor branch circuit short circuit and ground protection. In which two NEC sections are these requirements found?

NEC article 430.32, 430.52

200

Section ___ ___ required fuses  used for motor overload protection to be inserted in each ungrounded and grounded conductor if the supply system is a 3-wire, 3-phase AC with one conductor grounded.   (corner grounded DELTA)

430.36

200

What two formulas are used to calculate the Primary and Secondary currents in a transformer over 1000v in a Unsupervised location?


Primary I= kVA x 1000/V x 1.73

Secondary I x 1.25

200

________ do not have series ratings.

Fuses

200

When a overcurrent occurs on a selectively coordinated system on the ______ OCPD opens to interrupt the overcurrent.

Nearest Line-side

300

According to the NEC, select the allowed uses for a magnetic motor starter

motor controller, Motor overload protection

300

where can you find the requirements for the disconnecting means of an adjustable-speed drive system?

430:128

300

Note 1 to table 450.3(A) permits an OCPD of the next higher ________ if the calculation does not correspond to an available OCPD size.

Commercially available size

300

What is the biggest disadvantage of a series rated system, when under certain Short circuit conditions ?

The Line-side OCPD must open to protect the load-side circuit breaker

300

Ground-fault protection of equipment is a protective system intended to provide protection for damaging ____ fault currents.

Line-to-Ground

400

A single-phasing condition subjects a 3-phase electric motors to the worst possible case of ______ ____.

Voltage Imbalance

400

The ampere rating of the disconnecting means is required to be at least _______of the sum of all currents at he rated-load condition determined in accordance with 440.12(b)(1)

115%

400

For transformers with a high-inrush applications where the overcurrent device is sized close to the full-load current, An _______ fuse may be preferred to prevent nuisance openings. ( 1000 volts, nominal, or less)

Time-delay

400

Adequate OCPD interrupting rating , by itself _____ensure that load-side electrical equipment will be provided with adequate short-circuit protection

Does not

400

Where is GFPE not allowed to be installed on transfer switches of essential electrical systems?

Load-Side

500

what equipment  can be used to provide motor controller/overload protection,, 

Adjustable speed drive, contactor with overload relay Electronic overload protection, soft-start motor controller

500

A controller serving more than one motor-compressor or a motor-compressor and other loads is required to have a continuous-duty full-load current rating and a locked-rotor current rating not less than the combined load as determined in accordance with ______?

440.12(b)

500

what formula would you use to calculate primary current of a transformer 1000 volts or less.

(kVA x 1000)/ 1000

500

Most often, the SCCR for fusible panelboard and switchboards is determined by the interrupting rating of the fuses in the equipment up to a maximum of _____.

200kA

500

According to the NEC, GFPE is required if the feeder disconnect is rated 1000 Amperes or more and is installed on a solidly grounded wye system of more than _______

150V to ground.