Conductors
General
Standards
switch / Receptacles
More stuff
100

Electrical conductors installed in a cold storage warehouse could be considered located in a _______

Damp Location

Locations, Damp 100

100

What are the requirements for a receptacle installed directly over a bathtub or shower.

Recepticals can not be installed over a bathtub or shower stall.

406.9 (C)

100

What are the conductor materials covered in the NEC

Copper 

Copper-clad Aluminum

Aluminum

310.3(b)

100

The installation and use instructions may be provided in the form of printed material, quick response (QR) code, or the address on the Internet where users can download the required instructions. 

True or False

True 110.3(b)

100

Electrical equipment shall be installed in a __________ & _______  ________

Professional and skillful manner.

200

which of the following is/are characteristic(s) of good insulation?

Ability to withstand heat

Long life

Mechanical flexibility

Resistance to moisture

200

What is the minimum ampacity rating of a receptacle.

15 Amps

200

What causes conductors to heat up when in use

Current

310.14 (a) (3) info

200

a device box with a receptacle would be considered a/an _________


Outlet

200

 a splice in a conductor to be covered with an insulation ______________________________

equivalent to the conductor’s insulation or with an identified insulation device.

110.14(b)

300

What is the largest sized solid conductor permitted to be installed in a raceway

10 AWG


310.3(c)

300

_______________ rating associated with the ampacity of a conductor shall be selected and coordinated so as not to exceed the lowest temperature rating of any connected  termination  , conductor, or device

The Temperature

110.14 (C)

300

The five primary methods of terminating a wiring device are?

back wire

speed wire

side wire

pre-terminated leads (leaded)

and modular

300

What are the Basic Components of Switches and Receptacles' 

terminals

mounting strap

face plate. 

Receptacles also include contacts 

switches have actuator

300

The temperature rating associated with the ampacity of a conductor shall be so selected and coordinated as to not exceed the lowest temperature rating of any connected   ?  

conductor 

termination 

device 

110.14 (c)


400

The width of the working space in front of electrical equipment 1,000 volts or less shall   ?  

 allow at least a 90° opening of equipment doors

 not be less than 30" wide or the width of the equipment (whichever is greater)  

400

There are three conductor types defined in the NEC what are they _________ __________ ________

Bare

Covered

Insulated

400

Equipment that is listed, labeled, or both, or   ?   shall be installed and used in accordance with any instructions included in the listing, labeling, or identification.

Identified for a use

110.3 (B)

400

A piece of electrical equipment with a UL label on it shall be installed in accordance with any   ?   included in the listing or labeling.

Instructions

110.3 (B)

400

What are the following are the prime characteristics of a good insulation for conductors 600 volts and less:

Long Life

Slow aging

Resistance to Moisture

Mechanical Flexibility

500

 where the white or gray conductor of a cable assembly is used as a switch loop for circuits of 50 volts or more, the switch loop must be permanently reidentified as an ungrounded conductor by   ?  .

marking tape, painting, or other effective means of a color other than white, gray, or green

200.7(c)(1)

500

Electrical equipment provided with ________   ______ shall be installed so that walls or other obstructions do not prevent the free circulation of air through the equipment.

Ventilation Openings

110.13 (B)

500

Outlet devices shall have an ampere rating that is not less than

 the load to be served and shall comply with 210.21(A) and (B). 

210.21

500

There are four sources of heat that will have an effect on the insulation of a conductor; which can be accumulative. 

What are they

Ambient Heat

Heat Generated by Current Flow

Adjacent Load-Carrying Conductors

Heat Containment

 310.15(A)(3) Informational Note 1.

500

Accepted industry practices are described in  _______ Standard Practice for Good Workmanship in Electrical Construction, and other ANSI-approved installation standards.

. ANSI/NECA l-2015 

110.12 Information note