Classifications
Classifications
Nec Code
100

What is the classification of any area below grade within 20 feet of an outdoor gas pump?

Class 1 Div. 1

100

Areas 20ft of more horizontally away from fuel pumps are classified as 

unclassified

100

what article covers motor fuel dispensing facilities

514

200

What is the classification of an area within 10ft, in all directions, of a fill pipe?

Class 1 Div. 2

200

Area within 5 feet horizontally from aircraft power plants or fuel tanks are classified as

Class 1 Div 2

200

What article covers aircraft hangars

513


300

What is the classification of any space within the pump enclosure higher than 4 feet? 

Class 1 Division 2 

300

Areas not suitably cut off from hangars are classified as 

Class 1 Div. 2

300

Underground wiring shall be installed in _____ when installed below a class 1 location?

Threaded RMC or IMC 511.8

400

what is the space within the interior of the pump enclosure up to 4 feet high classified as?

Class 1 Division 1

400

What is the classification of an area within 18'' of the ceiling in a commercial garage that is servicing an vehicle fueled with natural gas

class 1 division 2

400

what article covers commercial garages 

511

500

What is the classification of any area below grade in a commercial garage with mechanical ventilation that changes air at least 5 times per hour 

Class 1 Division 1

500

Alcohol based windshield washer fluid is classified as what

unclassified

500

What table covers motor fuel dispensing facilities

514.3 (B) (1)