Condensate polishers
Regen system
CPS General Knowledge
Waste Recovery System
Do you think you know Don?
100

The demineralizers and associated condensate piping are designed at ______ PSIG

700

100

Minimizing the transfer of cation resins to the ARV prior to caustic draw can help reduce the production of

resin fines (due to osmotic shock)

100

air Scrubbing and back washing resin helps remove ______ from the resin bed 

Iron

100

at >10psig this Alarm will come in

Quartz filter High D/P

100

As a chem tech, Don's favorite duty area to work was ______

condensate polisher

200

When removing a DMV from service @ >80% power you must first ensure there are _______ vessels in service.

6

200

Cation resin is regenerated with ______ % acid

8

200

a CPS system differential pressure of 62 psid can result in this condition

condensate polisher bypass

200

At this level the WRS will will automatically start the low pit pumps

40%

200

___________ is a great movie from 2006 according to Don

Idiocracy

300

_____________ is the Maximum flow rate for a DMV

4800 GPM

300

A complete regenerated resin bed must rinsed down to this value _____

<0.1 uS/Cm

300

when transferring resin, the receiving vessel must have a ______, _______, and a ______ open 

vent, drain, and resin inlet valve

300

to start a quartz filter back wash you must first have a minimum level of

20% in the low pit

300

_______ is Don's favorite fish to pursue in the fall 

Striped Bass

400

The ________ valve equalizes pressure across the __CP2 valve prior to opening.

____CP4 or "Z" valve

400

The 2 most important valves in the regen system are the ____ and ____

Lh and Ph

400

Leaving cation resin behind in the Mix and Hold vessel may result in

creating a salt shaker

400

the WRS will automatically bypass the raw water basin at this conductivity

> or = 400 uS/cm

400

before Don was a chem tech, his favorite brand of tools was   _____________

Snap-on

500

With "H" bus de-energized for an outage what action must be taken in the condensate polisher system

isolate seal water to the high and low pit pumps

500

This regen step is the best step to let the resins soak

step 45

500

Receiving the wrong grade of caustic for the condensate polishing system can result in this condition

increased chlorides in the steam generators

500

At 10% level this Alarm will come in

low level in the low conductivity waste pit

500

Although Don is a Jersey guy he prefers this Pennsylvania favorite breakfast meat to Pork roll or Taylor ham ( you know who you are )

Scrapple