In the Zone
Interlocks
Name the Tank
CPC
CPC 2
100

This ventilation system maintains a pressure more negative than atmosphere but a higher pressure than Zone 2

What is Zone 3

100

A PAHH condition at this location would activate your safety train interlocks at LCS 261A and 261B

What is Sand Filter Inlet Plenum

100

This vessel sends MST/Sludge Solids to the SRAT 

What is PRFT

100

On a loss of power, the PRFT/SEFT to SRAT three-way valve would fail in this position

What is As-Is 

100

The SME condenser is cooled by this medium. 

What is Process Cooling Water

200

Along with the SCT and WTC, this is the only other Zone 2 area supplied by fresh outside air

What is Manipulator Repair Shop/Regulated Machine Shop 

200

While glycolic acid is being added to the SRAT, this valve is interlocked closed to prevent an unwanted chemical reaction 

What is Nitric Acid Addition Valve

200

The MWWT rests on this tank

What is SMECT

200

this pump has in-line pH monitors and is designed to run continuously. 

What is SMECT Sample Pump

200

If the MWWT Water Removal Valve is open, condensate will be directed to this vessel. 

What is SRAT

300

To avoid interlock shutdown, the analytical lab supply fan and the fan supplying this area must be started within 30 seconds. 

What is Level 1 North/Level 3 West



300

If the LPW priming valve for the SME Transfer Pump didn’t close in time, you would receive this alarm at the console. 

What is Priming Overtime 

300

This tank provides emergency backup for melter cooling water heat exchangers 

What is Clean Condensate Tank

300

The SRAT heating coil steam supply valve can be in either CLOSE or this position, where it can control for either flow or temperature. 

What is MODULATE

300

The temperature of the MST/Sludge Solid mixture in the PRFT is maintained within this band. 

What is 20-30 degrees Celsius. 

400

These are the two main functions of an ASU cooling coil. 

What is cooling and dehumidification 

400

HCV1899 on the Process Chilled Water system will interlock open if a pump is running and this other condition is met in order to maintain flow. 

What is both chiller inlet valves closed 

400

The transfer of RSS to SWPF from tank 49 at the tank farm occurs via a jumper placed in the cell where this vessel is housed.

What is the Recycle Waste Tank

400

The CDC transfer pump adds this to the SME through the isolation pot block valve

What is Spent Frit or Decon Frit 

400

The SRAT cooling coil return valve will interlock closed on a High Radiation Alarm as well as this other condition. 

What is SRAT heating coil steam supple valve open. 

500

This Zone 3 controller becomes inactive for steam valve control when humidity rises above 55%.

What is the Supply TIC

500

This 210-S ventilation system will interlock the supply fans off if a Zone 2 inlet pressure HIHI is received 

What is Regulated Area HVAC

500

The air separator in the hot water system removes entrained air and directs it to this tank to be vented. 

What is Hot Water Expansion Tank 

500

PVV total flow is controlled by this component

What is Air Dilution Valve (CMA)

500

Nitric Acid can be added to the DWTT for this purpose. 

What is Tank Deconning