Patient Care Power
Homes on Wheels
Wet & Bonded
Fill, Volts & Fine Print
Pot & Pads
200

A nursing home provides 24-hour care for at least this many persons.

What is 4?

200

A mobile home may have not more than one power-supply cord of this rating.

What is 50 A? (550.10(A))

200

Pool equipotential bonding conductor: solid copper of at least this size.

What is 8 AWG? (680.26)

200

Unless specifically approved for it, surface metal raceway is not permitted in this type of location.

What is a wet location? (386.12)

200

This new 2023 article covers cannabis oil extraction using flammable materials.

What is Article 512?

400

Minimum receptacles at a Category 2 patient bed location.

What is 8? (517.18(B))

400

Minimum height of the bottom of a mobile home service disconnect above grade.

What is 2 ft? (550.32(F))

400

Pool feeder or branch-circuit EGC: insulated copper, not smaller than this.

What is 12 AWG? (680.7)

400

Splices in surface metal raceway may fill no more than this percent of its area.

What is 75%? (386.56)

400

Name any one flammable solvent from the 512 informational note.

What is butane, ethanol, hexane, pentane, propane, or LPG? (512.20(B) Inf. Note)

600

Minimum receptacles at a Category 1 patient bed location.

What is 14? (517.19(B)(1))

600

Ranges and dryers in a mobile home get this many wires, because the neutral is never the EGC.

What is 4-wire? (550.16(A))

600

Perimeter surfaces within this distance of the water edge get bonded.

What is 3 ft? (680.26(B)(2))

600

Cable trays with conductors over this voltage need DANGER signs no more than 10 ft apart.

What is 600 V? (392.18(H))

600

The base plate of a wireless charging primary pad is made of this kind of metal.

What is nonferrous? (625.101)

800

A line isolation monitor alarms at this total hazard current.

What is 5 mA? (517.160)

800

RV park calc: each 50 A site is figured at this load.

What is 12,000 VA? (551.73(A))

800

A vinyl-liner pool needs a water bond with at least this much conductive surface.

What is 9 sq in.? (680.26(C))

800

Control/signal cable in a 6 in. or shallower ladder tray: fill limit of this percent.

What is 50%? (392.22(A)(2))

800

Where snow is plowed, a primary pad must be installed flush with or here.

What is below the surface? (625.102(C)(1))

1000

An OR needs at least 36 receptacles; this range must be on normal or a second critical-branch source.

What is 12 to 24? (517.19(C))

1000

Percent of existing and of new RV sites that need a 50 A receptacle.

What are 20% and 40%? (551.71)

1000

Above this voltage to ground, a pool pump motor needs an SPGFCI instead of a GFCI.

What is 150 V? (680.21(C))

1000

Surface metal raceway at 300 V or more needs metal at least this thick.

What is 0.040 in.? (386.12(2))

1000

Horticultural lights on cord over 150 V to ground use this instead of a regular GFCI.

What is an SPGFCI? (410.184 Exception)