Water Supply
Pressure
Instrument Air
Condensate
Bonus
100

What system is used to supply the plant hose reels?

Service water system

100

What is the minimum flow for the service water pumps?

291gpm

100

What should the normal dewpoint be?

-40

100

What is the purpose of the condensate system?

To regulate and recycle steam used throughout the plant

100

What is Tepid water defined as?

Water with a temperature between 60-100 degrees F

200

What system is used to supply the Closed Cooling Water makeup tank?

Demin Water

200

What is the design flow for the service water pumps?

1000gpm

200

What design and how many air compressors will be used at DBAPS?

3x50% Air-cooled rotary screw compressors

200

What is the purpose of the ammonia that is injected into the condensate?

 control pH

200

How many hose reels are located throughout the plant?

11

300

What system is used to supply the Tepid skid?

Potable Water System

300

What is the design flow for the condensate pumps?

3928gpm

300

What is the normal output pressure for the IAS?

90psig-125psig

300

Where is ammonia injected into the condensate header line?

Downstream of the Gland Steam Condenser

300

What two sources of water are combined and supplied to the TCA Coolers during start up?

Demin and condensate

400

What supplies cooling water to the ECA pumps?

Service Water Sysytem

400

What is the flow pressure for the potable water system?

60psi

400

What is the total number of air recievers?

5
400

During a startup, how does the condensate system supply feed water?

The LP drum is bypassed and the BFP takes suction directly from the discharge of the condensate pumps

400

What supplies the EVAP cooler sump and what makes it different?

Demin water first passes through the calcite filters before reaching the EVAP Cooler Sump

500

What system is used for compressor blade washing?

Demin Water

500

What is the discharge pressure of the High Pressure demin pumps?

483psi

500

How often does the air dryer towers switch roles?

Every 5 minutes

500

What is the normal level in the condensate tank?

74.25"

500

Condensate is used as attemperating water for the desuperheaters. How many are there?

7