Domestic
Commercial
Cable calcs
Cable calcs 2
Mixed questions
100

When calculating the length of a circuit,it is important to include...

The cable drops to switches/sockets

100

Diversity formula for cookers in commercial

Not applied 

100

Iz formula

In divided by correction factors

100

What is the maximum permitted voltage drop for a lighting circuit?

3%

100

How can poor floor plan design negatively affect cable selection and protective device choice?

Longer cable runs increase voltage drop and earth fault loop impedance, possibly requiring larger cables or lower-rated protective devices.

200

Minimum height of a socket 

450mm from ffl to centre of accessory 

200

It is recommended to have ... instead of switches in places where there is constant movement of objects/people 

sensors (PIR as an example)

200

Voltage drop formula

V.d= mV/a/m times Ib times L divided by 1000

200

What is the maximum permitted voltage drop for other circuits such as sockets?

5%

200

Why must electrical symbols on a floor plan match those in the drawing legend?

To avoid misinterpretation, installation errors, and non-compliance with design specifications.

300

Maximum height of a switch

1200mm from ffl to centre of accessory 

300

Lighting diversity formula

90% of Ib

300

where is R1+R2/m value found ?

OSG Table I1 

300

Cc value

1 if above ground
0.9 if bellow ground

300

What information should be included on an electrical floor plan to allow another electrician to install the system without further explanation?

Circuit references, accessory symbols, switch lines, cable routes, scale, legends, and distribution board location.

400

Where should the CCU ( Customers consumer unit) be placed?


Accessible yet hidden space ( utility room/cupboard etc)

400

Diversity formula for power circuits (e.g FCUs for hand dryers/ hair dryers)

100% of Ib of the first appliance and 75% of Ib for the rest of the appliances 

400

R1+R2 formula

R1+R2/m times L times 1.2 divided by 1000

400

How many metres squared can a radial circuit wired in 2.5mm cover?

50m squared

400

Why must all applicable correction factors be applied before finalising cable size selection?

Because ignoring any factor may result in a cable that overheats or fails to meet design current requirements under real conditions.

500

The diversity formula for cooker circuits

Ib - 10A, 30% of the remainder, +10A (+5A if socket is incorporated in the cooker switch) 

500

What scale is most commonly used for electrical floor plans?

1:50

500

Name first 7 steps of cable calcs

ib, in, correction factors, Iz, install. method, It, Actual voltage drop. 

500

Whats the maximum area of a room that a ring circuit wired in 2.5mm can cover ?

100 metres squared

500

A circuit has design current Ib of 24 A. After applying temperature and grouping factors, a 2.5 mm² cable can carry only 21 A. What design decision must be made and why?

Increase cable size (e.g. 4 mm²) because Iz must be ≥ In ≥ Ib to comply with BS 7671.