Core
Type 1
Type 2
Type 3
Misc.
100

This international treaty addresses ozone-depleting substances and their alternatives.

Este tratado internacional aborda las sustancias que agotan la capa de ozono y sus alternativas.

What is the Montreal Protocol?

¿Qué es el Protocolo de Montreal?

100

The definition of a small appliance includes; product manufactured, fully charged, and hermetically sealed in a factory containing what amount or less of refrigerant.

What is five pounds or less? (Pg. 16 para 2)

100

To reduce recovery time, you can do this to the recovery cylinder to reduce recovery time.

What is cooling the recovery cylinder? (Pg. 22 para 1)

100

Type 3 certification will allow a technician to work with these type of appliances.

What is low-pressure appliances? (Pg. 24 para 1)

100

These 4 major components of a refrigeration cycle include what?

What is the compressor, the metering device, the evaporator and the condenser? (Pg.3)

200

This process means to extract refrigerants from and appliance and clean the refrigeration for reuse in equipment of the same owner.

Este proceso significa extraer refrigerantes de un aparato y limpiar la refrigeración para reutilizarla en equipos del mismo propietario.

What is Recycling?

¿Qué es el reciclaje?

200

This is where you would put the hoses connected to the gauge manifold when recovering refrigerant from a household refrigerator or any other appliance to improve the speed of recovery. 

What is the low and high-side access valves. (Pg. 17 para 10)

200

This is the recovery level of evacuation during recovery you must achieve for a very-high pressure appliance.

0” Hg (pg. 22)

200

When leak testing a low-pressure centrifugal chiller with nitrogen, this is the maximum test pressure in PSIG.

What is 10 PSIG. (Pg. 24 para 4)

200

In a refrigeration system this device/component rejects heat to the outside from the refrigerant. 

What is the condenser?

300
This device is used to determine the general area of a small leak.

What is an electric or ultrasonic leak detector?

300

Non-condensable gas in the refrigerant can be checked for by using this kind of chart.

What is a pressure-temperature (PT) chart? (Pg.18 para 2)

300

This is the recovery level of evacuation during recovery you must achieve for a medium-pressure appliance with less than 200lbs of refrigerant. 

10” Hg (pg. 22)

300

The system should be checked for leaks if, during a standard vacuum test, the pressure in a system rises from _____mm Hg to a level above _____mm Hg.

What is 1mm Hg to a level above 2.5mm Hg? (Pg.24 para 7)

300

This device/component allows for heat to be rejected in the high pressure line and allow for heat to be absorbed in the low pressure line.

What is the compressor?
400

In the event of a large release of CFC, HCFC, HFC, HFO, HC, or any other refrigerant in a contained area, you must follow one of these two steps.

What is using a self-contained breathing apparatus (SCBA) or leaving the area?

400

When filling a charging cylinder with a regulated refrigerant, you must _____ the refrigerant that is vented off the top.

Recover (pg. 16 para 10)

400

This equipment/part is required to be on gauge hoses that are connected to the recovery unit to the tank to minimize refrigerant release when the hoses are connected or disconnected.

What is Self-sealing connectors or hand valves? (Pg.21 para.8)

400

Before disposing of a low-pressure appliance, the refrigerant must be recovered or evacuated to a level of X mm of Hg absolute.

What is 25 mm of Hg absolute? (Pg. 26 para 6)

400

This happens when vapor has heat added above its vaporization point.

What is superheat?

500

This refrigerants can be slightly flammable and have no ozone depletion potential but do have a very small effect on global warming.

What is an HFO?

500

This accessory is typically used on small appliances and is a straight piece of tubing that is entered using a piercing access valve to add or remove refrigerant from a small appliance.

What is the service aperture or process stub? (Pg. 17 para 7)

500

This accessory, that is used for checking refrigerant moisture, is located in the liquid line, immediately downstream, after the liquid-line filter drier.

What is a sight glass? (Pg. 23 para 1)

500

To convert from an absolute pressure (psia) to gauge pressure (psig) subtract this amount from the absolute pressure.

What is 14.7? (Pg.26 para 9)

500

If a chiller with a charge of 200lbs of an ozone-depleting refrigerant has passed the initial verification leak test, a follow-up verification test must be conducted within this many days.

What is 10 days? (Pg. 25 para 9)