What is the power loss in watts of a conductor that carries 24A and has a voltage drop of 7.2V?
What is 175W
The requirement to maintain a 3 foot vertical clearance from the edge of a roof does not apply to the final conductor span where the service drop is attached to_____________.
What is the side of a building
For wiring methods "on or attached to the surface, or behind access panels designed to allow access" is know as
What is exposed
What is the Ac OHMS to neutral resistance for 100ft of 3 awg copper conductor
What is 0.025
True or false: An overload is the same as a short circuit or ground fault.
What is False
A nursing home is an area used for housing and nursing care, on a 24 hour basis, of ______or more persons.......
What is four
What is the feeder/service calculated load for a 4kw dryer?
What is 5 KW
True or false: Type NM cable shall not be used in one- and two family dwellings exceeding three floors above grade.
What is False
Receptacles shall not be grounded or ganged in enclosures unless the voltage between adjacent devices does not exceed ________.
What is 300V
Both units of a duplex apartment require a 100a main; the resulting 200a service will require ________copper conductors.
What is 3/0AWG
If the primary voltage of a transformer is 480v and the secondary voltage is 240V, the turns ration is what?
What is 2:1
FMC shall be secured and supported __________
What is intervals not exceeding 4 1/2 ft
What is the feeder service calculated load for one 6kw and two 3 kw cooking appliances
What is 9.3 kw