Fire Rated Door Assemblies
Storage
Utilities/Electrical
Utilities/Plumbing-Med Gas
Environment of Care
100
On what schedule is Fire Rated Door Assemblies require inspection?
What is annually.
100
What is the maximum distance between the bottom of the sprinkler head and the height of storage permitted in a storage room?
What is 18".
100
For what duration of time must the emergency powered generator be tested under load monthly excluding start up and cool down?
What is 30 minutes.
100
What is the most common issue concerning med gas zone valves throughout the hospital?
What is blocking access to them.
100
What is the pressure required for a soiled/dirty room, positive or negative?
What is negative.
200
What is the maximum undercut permitted by code in a fire rated door?
What is 3/4"
200
What is the classification for medical equipment storage?
What is low hazard?
200
Fill in the blank: Emergency back up generators shall be tested at ___________ of their name plate rating.
What is 30%.
200
How often is an eyewash station required to be tested for proper functionality.
What is weekly.
200
What is required before going above ceiling in the Lab, NICU, and in Dietary Food Prep Area?
What is a HEPA cart or approved barrier.
300
What is the minute rating required on the fire door within a 1 hour fire rated wall?
What is 45 min.
300
What is the clearance code requirement for accessing an electrical panel?
What is 36".
300
What is the distance requirement for a GFCI receptacle in relation to a water source?
What is 6' or less.
300
In addition to the label listing who can turn off a med gas zone valve, what additional label is required for a med gas zone valve?
What is a label listing all the rooms/areas that the zone valve supports.
300
What is the violation when items are stored in hallways that lead to stairwells?
What is blocked egress.
400
What are the only type of fire rated doors separating two compartments that do not have to positively latch?
What is double egress fire rated door assemblies.
400
What is the maximum number of O2 cylinders permitted in an O2 storage area?
What is 12.
400
How often shall LIM's be tested?
What is monthly?
400
What is the GPM (Gallons Per Minute) required for an eyewash station?
What is .4 gallons per minute.
400
What is considered proper storage for bottled gas?
What is that every cylinder is chained or secured individually.
500
For storage rooms greater than 100 sq. ft., what must the fire rated door assembly be equipped with?
What is an automatic door closer.
500
What must be positioned differently in a storage or electrical/mechanical room if there is no ceiling?
What is the sprinkler heads. They must be pointed upward toward the deck.
500
What is required if the emergency backup generator is not tested under the proper load each month?
What is an annual load test.
500
Who can turn off a med gas zone valve?
Who is, Nurse Manager, Facilities, Fire Department, or Respiratory Therapy.
500
What is required immediately upon finding a Life Safety violation or discrepancy?
What is an Interim Life Safety Measure (ILSM) Assessment.