Core of the matter
Type I personality
Type II to Tango
Type III dog night
Potpourri
100

These are used for new refrigerant

Disposable cylinders

100

According to ASHRAE standard 34 refrigerant safety classifications, these are the most dangerous

B3
100

This is restricted to technicians who are EPA certified in refrigerant recovery.

Sale of refrigerants

100

On refrigeration units that use an open compressor; this is most likely to leak if the unit is not used for several months.

the rotating shaft seal, or compressor shaft seal

100

When evacuating a system, the use of too large a vacuum pump can cause this. 

Trapped water in the system to freeze.

200

This is colored red on a manifold gauge set

High Pressure Gauge

200

This type of oil that is most commonly used in stationary refrigeration applications with HFC-134a refrigerant.

Ester-based oil

200

In a refrigeration system, the component directly following the evaporator is the ______. 

Accumulator

200

A local municipal water supply, should be used as the primary water source for cooling for this.

the condenser of a water-cooled recovery unit

200

These steps may be taken to prevent air accumulation into an idle low pressure refrigeration system. 

System pressure should be maintained slightly above atmospheric.

300

A refrigerant mixture that acts like a single-component refrigerant over its entire range is called

 Azeotropic

300

Under the conditions of ARI 740-1993, recovery devices that were manufactured after November 15, 1993 and are used for recovery of refrigerant from small appliances must be capable of this 

recovering 90% of the refrigerant when the compressor is operating or achieving a 4 inch vacuum

300

R-410A requires a high-pressure manifold gauge and hose set. They must have what ratings per the EPA

4000 psig burst pressure and 800 psig working pressure.

300

The evaporation temperature of R- 410a at 100 psig is approximately this.

30 degrees F.

300

Commercial and industrial process refrigeration systems must be repaired when the leak rate exceeds what percent of the charge per year.

Thirty percent / 30 %

400

These leak from a system in uneven amounts due to different vapor pressures.

Blended refrigerants (zeotropic)

400

These conditions can cause excessive pressure on the high side of an active self-contained recovery device

a closed recovery tank inlet valve, and/or excessive air or other non-condensables in the recovery tank

400

The proper charging method for blended (non-azeotropic) refrigerants (400 Series) is to use a remove the charge from the cylinder as a what?

Liquid

400

excessive superheat on a high-pressure system is an indicator of this. 

Excessive superheat

400

System water pumps, the recovery compressor, and the recovery condenser water should all be on _____.

When recovering vapor from a low pressure refrigeration system

500

These gases helps form Earth's protective shield from UV radiation.

Stratospheric ozone

500

EPA regulations require the capture of at least 80% of the refrigerant from a small appliance with a non-operating compressor if the technician is using this.

a system-dependent (passive) recovery unit or a self-contained (active) recovery unit.

500

In a refrigeration system with a TXV, the component directly following the condenser is this.

Liquid Receiver 

500

When there is excessive moisture collecting in the purge unit of a low pressure refrigeration system indicates this. 

the condenser or chiller barrel tubes are leaking.

500

Both CFC-11 and HCFC-123 chillers require purge units because of this. 

the system operates below atmospheric pressure